Sensopress_LCD_Rev_00_Eng.doc Eng
18
Figure 16
By pushing the
Yes/+
button it is possible to make the zero setting and on the display it is shown the
writing
SAVING
…….for a few seconds, after which the device turns in the
AUTO
Mode.
By pushing the
Menu
button there is the possibility to go out from the calibration procedure without
saving the zero. It turns back to the
AUTO
mode.
5.1.2
High Level Calibration
It is possible to enter the calibration of high level by pushing the
Yes/+
button after entered the
CALIB
.
Make sure the sensor is put through the water column which needs to be set-up.
On the display is visualized the screen of Figure 17.
Figure 17
With the
Yes/+
and
No/-
buttons it is possible to set-up the water column value to which the high level
calibration needs to be done and to which is put through the sensor.
Push the
Menu
button to enter the saving of the high setting level and it is visualized the screen of
Figure 18.
Figure 18
By pushing the
Yes/+
button
it is possible to do the saving of the
set-up high level and on the displays
it is given the writing
SAVING
….. for a few seconds, after this the device turns in the
AUTO
mode.