SETTING ALARM OUTPUT
Measurand: Current
Low setpoint: 50 A
High setpoint: 120 A
Hysteresis (deadband): 1%
Alarm ON delay time: 1 second
Discrete output: DO1
Change Setting
(SETTINGS)
Discrete I/O Setting
(DIO)
Discrete output function
(DO1-FUNC)
ALARM : Alarm output
Discrete output mode
(DO1-TYPE)
N-O : Normally open
Alarm Output Setting
(ALARM)
Measurands
(I1-3)
High setpoint
(HIGH)
120A
50A
Low setpoint
(LOW)
Hysteresis (deadband)
(HYSTERES)
1.0
1
Alarm ON delay time
(ON DELAY)
DOUT
Alarm output
(OUTPUT)
■
SETTING ENERGY COUNT OUTPUT
Measurand: Active energy
Pulse weight: 1 kWh/count
ON pulse width: 500 msec.
Discrete output: DO2
Change Setting
(SETTINGS)
Discrete I/O Setting
(DIO)
Discrete output function
(DO2-FUNC)
ENERGY : Energy count pulse
Discrete output mode
(DO2-TYPE)
N-O : Normally open
Energy Setting
(ENERGY)
Pulse output 1
(COUNT1)
EP : Active energy
Pulse weight 1
(WEIGHT1)
1.0
Pulse width 1
(DURATION1)
500
Tariff switching
(TARIFF)
DISABLE