Hold down 2 sec.
Enter Passcode
0000 thr. 9999 (0000)
■
PROGRAMMING FLOWCHART
ENERGY : Total energy
MAX/MIN : Max/Min values
DEMAND : Average
PEAK : High tariff (
*
)
OFF PEAK : Low tariff
NO : Cancel
YES : Reboot
0000 thr. 9999
Bargraph indication
setting
(BAR)
Input Setting
(INPUT)
System configuration
(SYSTEM)
1P2W : Single-phase/2-wire
1P3W : Single-phase/3-wire
3P3W-B : 3-phase/3-wire balanced
3P3W-UB : 3-phase/3-wire unbalanded (
*
)
3P4W-B : 3-phase/4-wire balanced
3P4W-UB : 3-phase/4-wire unbalanced (
*
)
CT rating, primary
(CT-PRI)
1 thr. 20 000 A (1 or 5A)
CT rating, secondary
(CT-SEC)
1 thr. 5 A (1 or 5A)
VT rating, primary
(VT-PRI)
50 thr. 400 000 V (110V)
VT rating, secondary
(VT-SEC)
50 thr. 500 V (110V)
AC frequency
(FREQUENCY)
U1N : Voltage (
*
)
I1 : Current
Low-end cutout, current
(CUTOUT-I)
0.0 thr. 99.9% of the rating (1.0%)
Low-end cutout, voltage
(CUTOUT-U)
0.0 thr. 99.9% of the rating (1.0%)
Maximum value
(UPPER)
Minimum value
(LOWER)
(
*
) or ( ) : Factory setting
Device information
(DEV.INFO)
: Go up one level in the chart
: Select
: Move between menu items
Reset count
(RESET)
NO : Cancel
YES : Reset
Reset alarm
(CLR ALARM)
Switch tariff
(TARIFF)
Reboot device
(REBOOT)
Change Passcode
(PASSCODE)
Execute
Loop test
*
1
Change Setting
(SETTINGS)
PQS
PF THD
MAX
E PRG ESC
E PRG ESC
System configuration factory setting
54UL-1: 3P3W-UB
54UL-2: 3P4W-UB
[Loop Test]
Press button to switch among outputs. Press
buttons to increase/decrease output signal or to change output status (ON or OFF).
IU
PQS
PF THD
Model No. 54Ux
Firmware version No.
Serial No.
Following parameters
are programmable
I
U
P
Q
S
PF
F
THD
PHASE DIF
*
2
*
2
*
1. Simulated output without applying actual input signals.
*
2. Refer to “SETTING BARGRAPH INDICATION ” in “SETTING EXAMPLE” section.
MAX