54UL
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6488-B Rev.3 P. 24 / 32
Change Setting
(SETTINGS)
Demand Setting
(DEMAND)
Energy Setting
(ENERGY)
Average current
(I)
DIN : External discrete input
1 thr. 60 : Minutes (30)
Average power
(POWER)
DIN : External discrete input
1 thr. 60 : Minutes (30)
Pulse output 1
(COUNT1)
*
3
Pulse weight 1
(WEIGHT1)
0.1 thr. 10 000.0 :
kWh / kvarh / kVAh (1.0)
Pulse width 1
(DURATION1)
100 thr. 2 000 ms (100 ms increments)
(100)
Tariff switching
(TARIFF)
DISABLE (
*
)
ENABLE
Pulse output 2
(COUNT2)
*
3
Pulse weight 2
(WEIGHT2)
0.1 thr. 10 000.0 :
kWh / kvarh / kVAh (1.0)
Pulse width 2
(DURATION2)
100 thr. 2 000 ms (100 ms increments)
(100)
(
*
) or ( ) : Factory setting
*
3. Refer to "ENERGY COUNT TYPE" later in this section.
*
4. Refer to "ALARM OUTPUT SETTING" later in this section.
Discrete I/O
Setting (DIO)
Discrete output 1 function
(DO1-FUNC)
NO FUNC : Not used (
*
)
ENERGY : Energy count pulse
ALARM : Alarm output
Discrete output 1 mode
(DO1-TYPE)
N-O : Normally open (
*
)
N-C : Normally closed
Discrete output 2 function
(DO2-FUNC)
NO FUNC : Not used (
*
)
ENERGY : Energy count pulse
ALARM : Alarm output
Discrete output 2 mode
(DO2-TYPE)
N-O : Normally open (
*
)
N-C : Normally closed
Discrete input function
(DIN-FUNC)
NO FUNC : Not used (
*
)
DEMAND : Update demand
RESET E : Reset energy
CLR ALARM : Reset alarm
TARIFF : Switch tariff
Discrete input type
(DIN-TYPE)
N-O : Normally open (
*
)
N-C : Normally closed
DI
DO
DO
Alarm Output Setting
(ALARM)
Power ON delay time
(POWON DLY)
0 thr. 999 seconds (0)
Latching
(LATCHING)
DISABLE (
*
)
ENABLE
Measurands
*
4
I1-3
IN
3P4W 3.00
U12-31
U1N-3N
P
Q
S
PF
F
I1-3 AVG
IN AVG
3P4W 3.00
P AVG
Q AVG
S AVG
THDI1-3
THDIN
3P4W 3.00
THDU12-31
THDU1N-3N
UT12-31
High setpoint
(HIGH)
HIGH :
*
4 (0)
LOW :
*
4 (0)
Low setpoint
(LOW)
Hysteresis (deadband)
(HYSTERES)
0.0 thr. 99.9% (0.0)
0 thr. 999 seconds (0)
Alarm ON delay time
(ON DELAY)
DISABLE : Disable alarm (
*
)
DISP ONLY : Display only
DOUT1 : Discrete output 1 + display
DOUT2 : Discrete output 2 + display
Alarm output
(OUTPUT)
DO