ALARM OUTPUT SETTING
ID
*
1
DEFINITION
LOW SETPOINT
HIGH SETPOINT
UNIT
I1-3
Current, Line 1 thr. Line 3
0.000
20 000.000
A
IN
Neutral current
3P4W
3.00
0
20 000
A
U12-31
Delta voltage, Line 1 – 2, 2 – 3, 3 – 1
0.00
400 000.00
V
U1N-3N
Phase voltage, Phase 1 thr. Phase 3
0.00
400 000.00
V
P
Active power
-2 000 000 000
2 000 000 000
W
Q
Reactive power
-2 000 000 000
2 000 000 000
var
S
Apparent power
0
2 000 000 000
VA
PF
Power factor
-1.0000
1.0000
—
F
Frequency
45.00
65.00
Hz
I1-3 AVG
Average current, Line 1 thr. Line 3 (demand)
0.000
20 000.000
A
IN AVG
Average neutral current (demand)
3P4W
3.00
0
20 000
A
P AVG
Average active power (demand)
-2 000 000 000
2 000 000 000
W
Q AVG
Average reactive power (demand)
-2 000 000 000
2 000 000 000
var
S AVG
Average apparent power (demand)
0
2 000 000 000
VA
THD I1-3
THD, Current, Line 1 thr. Line 3
0.0
999.9
%
THD IN
THD, Neutral current
3P4W
3.00
0.0
999.9
%
THD U12-31
THD, Delta voltage, Line 1 – 2, 2 – 3, 3 – 1
0.0
999.9
%
THD U1N-3N
THD, Phase voltage, Phase 1 thr. Phase 3
0.0
999.9
%
UT12-31
Phase angle between voltages, Phase 1 – 2, 2 – 3, 3 – 1
-180
180
°
*1. Indicated while in alarm conditions.