47DT OPERATING MANUAL EM-9508-B Rev.7
MODE
PARAMETER
SETTING RANGE
SUB DISPLAY /
INDICATOR
MAIN DISPLAY
DEFAULT
VALUE
DECIMAL
POINT
POSITION
UNIT
Initial
Setting
Analog output 0%
adjustment
Adjustable range
-5 to +100%
:
(increasing)
(decreasing)
0% output
----
----
Analog output 100%
adjustment
Adjustable range
0 to 105%
:
(increasing)
(decreasing)
100%
output
----
----
Alarm
setting
Bank No.
1 to 8
to
----
----
Alarm output pattern
Normal, zone
,
----
----
LL alarm setpoint
-999.9 – 9999.9
/
to
10
-1
°C/°F
LL trip action
High trip, low trip
/
,
----
----
LL deadband
(hysteresis)
00.0 – 99.9
/
to
10
-1
°C/°F
LL ON delay time
000 – 999
/
to
----
100 ms
LL OFF delay time
000 – 999
/
to
----
100 ms
LL one-shot output
0000 – 9999
/
to
----
100 ms
LL coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
L alarm setpoint
-999.9 – 9999.9
/
to
10
-1
°C/°F
L trip action
High trip, low trip
/
,
----
----
L deadband
(hysteresis)
00.0 – 99.9
/
to
10
-1
°C/°F
L ON delay time
000 – 999
/
to
----
100 ms
L OFF delay time
000 – 999
/
to
----
100 ms
L one-shot output
0000 – 9999
/
to
----
100 ms
L coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
H alarm setpoint
-999.9 – 9999.9
/
to
10
-1
°C/°F
H trip action
High trip, low trip
/
,
----
----
H deadband
(hysteresis)
00.0 – 99.9
/
to
10
-1
°C/°F
H ON delay time
000 – 999
/
to
----
100 ms
H OFF delay time
000 – 999
/
to
----
100 ms
H one-shot output
0000 – 9999
/
to
----
100 ms
H coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
HH alarm setpoint
-999.9 – 9999.9
/
to
10
-1
°C/°F
HH trip action
High trip, low trip
/
,
----
----
HH deadband
(hysteresis)
00.0 – 99.9
/
to
10
-1
°C/°F
HH ON delay time
000 – 999
/
to
----
100 ms
HH OFF delay time
000 – 999
/
to
----
100 ms
HH one-shot output
0000 – 9999
/
to
----
100 ms
HH coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
NOTE 2: SUB DISPLAY/INDICATOR:
= ON,
= Blinking