228
47DT OPERATING MANUAL EM-9508-B Rev.7
MODE
PARAMETER
SETTING RANGE
SUB DISPLAY /
INDICATOR
MAIN DISPLAY
DEFAULT
VALUE
DECIMAL
POINT
POSITION
UNIT
Alarm
setting
P ON delay time
000 – 999
/
to
----
100 ms
P OFF delay time
000 – 999
/
to
----
100 ms
P one-shot output
0000 – 9999
/
to
----
100 ms
P coil at alarm
Coil energized at alarm,
de-energized at alarm
/
,
----
----
Main display blinking
at alarm
No blinking, blinking in 1.0,
0.5, 0.3 sec. intervals
,
,
,
----
Second
Bank copy
No copying, copy current
bank value to all banks
,
----
----
Advanced
setting
Event trigger mode
Normal, sampling hold,
peak hold,
valley (bottom) hold, peak-
to-peak hold
,
,
,
,
----
----
ON timing delay
000.0 – 999.9
to
----
Second
OFF timing delay
000.0 – 999.9
to
----
Second
Startup timer
00.0 – 99.9
to
----
Second
Averaging type
Moving average,
simple average
,
----
----
Averaging time
None, 2, 4, 8, 16, 32, 64,
128, 256, 512
,
,
,
,
,
,
,
,
,
----
Sample
Low-end cutout
OFF, ON,
absolute value ON
,
,
----
----
Low-end cutout
value
0.0 – 9.9
to
10
-1
°C/°F
Display color
Green (normal) to red
(alarm), green,
red (normal) to green
(alarm), red
,
,
,
----
----
Automatic return
time to Measuring
Mode
00 (automatic return
disabled)
01 – 99
to
----
Second
Transition time to
Lockout Setting
Mode
00 – 99
to
----
Second
Burnout
Upscale burnout,
downscale burnout
,
----
----
CJC sensor
CJC sensor disabled,
CJC sensor enabled
,
----
----
Display refreshing
rate
00.0 – 99.9
to
----
Second
Manual sub display
reset
Alarm setpoint display
automatically reset, alarm
setpoint display manually
reset
,
----
----
P output
No P output,
alarm setpoint LL,
alarm setpoint L,
alarm setpoint H,
alarm setpoint HH
/
,
,
,
,
,
,
,
----
----
Latching alarm
No latching,
output latched / measuring
continued,
output latched / measuring
stopped
,
,
----
----
Alarm power ON
delay
000.0 – 999.9
to
----
Second
NOTE 2: SUB DISPLAY/INDICATOR:
= ON,
= Blinking