45
47DT OPERATING MANUAL EM-9508-B Rev.7
3. SETTING INPUT TYPE
Set input type according to the thermocouple to use. Narrow span for the thermocouples K (CA) and J (IC) enables ac-
curate indication.
3.1 INPUT TYPE LIST
■
TEMPERATURE UNIT: °C
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
DEFAULT VALUE
TYPEK1
K (CA)
-230.0 to +1330.0
-200.0 to +1300.0
TYPEK1
TYPEK2
K (CA), narrow span
-50.0 to +530.0
-20.0 to +500.0
TYPE E
E (CRC)
-30.0 to +630.0
0.0 to 600.0
TYPEJ1
J (IC)
-130.0 to +880.0
-100.0 to +850.0
TYPEJ2
J (IC), narrow span
-50.0 to +430.0
-20.0 to +400.0
TYPE T
T (CC)
-230.0 to +430.0
-200.0 to +400.0
TYPE B
B (RH)
70.0 to 1830.0
400.0 to 1800.0
TYPE R
R
-30.0 to +1730.0
0.0 to 1700.0
TYPE S
S
-30.0 to +1730.0
0.0 to 1700.0
TYPE C
C (WRe 5-26)
-30.0 to +2330.0
0.0 to 2300.0
TYPE N
N
-230.0 to +1330.0
-200.0 to +1300.0
TYPE U
U
-230.0 to +430.0
-200.0 to +400.0
TYPE L
L
-130.0 to +880.0
-100.0 to +850.0
TYPEPR
(PR)
-30.0 to +1730.0
0.0 to 1700.0
■
TEMPERATURE UNIT: °F
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
DEFAULT VALUE
TYPEK1
K (CA)
-382.0 to +2426.0
-328.0 to +2372.0
TYPEK1
TYPEK2
K (CA), narrow span
-58.0 to +986.0
-4.0 to +932.0
TYPE E
E (CRC)
-22.0 to +1166.0
32.0 to 1112.0
TYPEJ1
J (IC)
-202.0 to +1616.0
-148.0 to +1562.0
TYPEJ2
J (IC), narrow span
-58.0 to +806.0
-4.0 to +752.0
TYPE T
T (CC)
-382.0 to +806.0
-328.0 to +752.0
TYPE B
B (RH)
158.0 to 3326.0
752.0 to 3272.0
TYPE R
R
-22.0 to +3146.0
32.0 to 3092.0
TYPE S
S
-22.0 to +3146.0
32.0 to 3092.0
TYPE C
C (WRe 5-26)
-22.0 to +4226.0
32.0 to 4192.0
TYPE N
N
-382.0 to +2426.0
-328.0 to +2372.0
TYPE U
U
-382.0 to +806.0
-328.0 to +752.0
TYPE L
L
-202.0 to +1616.0
-148.0 to +1562.0
TYPEPR
(PR)
-22.0 to +3146.0
32.0 to 3092.0
IMPORTANT
• The display accuracy is assured within the conformance range though indicating within the usable range is available.
• The bargraph lower and upper limits, analog outputs 0% and 100% are returned to the default values per input type
when the input type has been changed. All alarm setpoints of the current bank No. are disabled (reset to ‘-----’ status).
It is recommended to record the current settings as necessary.