background image

035-14527-000 REV A (599)

Form 650.77-N3U

26

Unitary Products Group

around the rear heat exchanger tubes. Vacuum loose 
scale and dirt from each tube.

7.

Clean - Replace all components in reverse order. Regas-
ket all surfaces which required a gasket. Reconnect all 
wiring. Reattach vent pipe and gas supply lines before 
restoring service to furnace. Restore electrical power, 
check gas supply piping for leaks, then verify furnace 
operation.

TROUBLESHOOTING

The following visual checks should be made before trouble-
shooting:

1.

Check to see that the power to the furnace and the igni-
tion control module is ON.

2.

The manual shutoff valves in the gas line to the furnace 
must be open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation.

Start the system by setting the thermostat above the room
temperature. Observe the system's response. Then use the
troubleshooting section in this manual to check the system's
operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self diagnostic capability. If a system
problem occurs, a fault code is shown by a blinking LED. It is
located behind a clear view port in the blower compartment
door. DO NOT remove the furnace blower compartment
panel OR turn off furnace power as either action will clear the
control's memory of the fault.

The control continuously monitors its own operation and the
operation of the system. If a failure occurs, the LED will indi-
cate the failure code. If the failure is internal to the control, the
light will stay on continuously. In this case, the entire control
should be replaced as the control is not field repairable.

If the sensed failure is in the system (external to the control),
the LED will flash in the following flash-pause sequences to
indicate failure status.

Flash sequence codes 1 thru 4 are as follows. LED will turn
on for 1/4 second and off for 1/4 second. This pattern will be
repeated the number of times equal to the code. For exam-
ple, six on flashes equals a number 6 fault code.

All flash code sequences are broken by a 2 second off period. 

CONTINUOUS FLASHING (1 sec on - 1 sec off): 

This indi-

cates that flame was sensed when there was not a call for
heat. With this fault code the control will also turn on both the
inducer motor and supply air blower. This fault would typically
be caused by a gas valve that leaks through or is slow clos-
ing.

1 FLASH: 

This fault code indicates that flame could not be

established. This no-light condition occurred 3 times during
the call for heat before locking out. This may be caused by
low gas pressure, faulty gas valve, faulty hot surface ignitor
or burner problem.

 

2 FLASH: 

This indicates that the normally open pressure

switch contacts are stuck in the closed position. The control
confirms these contacts are open at the beginning of each
heat cycle. This would indicate a faulty pressure switch or
mis-wiring.

3 FLASH: 

This indicates the normally open pressure switch

contact did not close at the beginning of the heat cycle. This
could be caused by a number of problems; faulty inducer,
blocked vent pipe, broken pressure switch hose or faulty
pressure switch.

4 FLASH: 

This indicates that a primary limit, or auxiliary limit,

or rollout limit switch has opened its normally closed contacts.
With this fault code the control will operate the supply air
blower and inducer. This condition may be caused by: dirty fil-
ter, improperly sized duct system, incorrect blower speed set-
ting, incorrect firing rate or faulty blower motor. The rollout
control is manually reset. If it has opened, check for proper
combustion air, proper inducer operation, primary heat

50A51-242 IGNITION CONTROL (P/N 031-01290-000) 

Normal flame sense current is approximately 

2.4 microamps DC (

υ

a)

Low flame signal control lockout point is    

0.15 microamps DC (

υ

a)

POWER SUPPLY POLARITY - 50A51-242 Control
Only      

If the power supply polarity is reversed, the fol-

lowing unit operation will occur. On a call for heat, the
inducer will run, the HSI will glow and the gas valve will
energize and the burners will ignite. The burners will
immediately extinguish and the unit will recycle. This will
occur 3 times and then the unit will lockout. A “7” flash
code will be displayed. This code means the flame could
not be established. This occurs because the control can-
not sense flame with the power supply polarity reversed.

Summary of Contents for P*DD & G8D-DN series

Page 1: ...MID EFFICIENCY GAS FIRED TUBULAR HEAT EXCHANGER SERIES MODELS P DU G8D UH Upflow Horizontal P DD G8D DN Downflow 57 120 MBH INPUT 035 14527 000 REV A 599 Form 650 77 N3U FOR YOUR SAFETY WHAT TO DO IF...

Page 2: ...ds 4 Paper bags boxes or other paper products Never operate the furnace with the blower door removed To do so could result in serious personal injury and or equipment damage CONTENTS GENERAL INFORMATI...

Page 3: ...arify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment or property damage may occur if ins...

Page 4: ...appliance when access is required for servicing and cleaning Eighteen 18 inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue ve...

Page 5: ...of all appliances located in the space NOTE Ducts must have the same cross sectional area as the free area in the opening to which they are connected The minimum dimension of rectangular ducts shall b...

Page 6: ...inting inks paint removers varnishes etc o Hydrochloric acids p Cements and glues q Antistatic fabric softeners for clothes dryers r Masonry acid washing chemicals VENTING CATEGORY I VERTICAL VENTING...

Page 7: ...0 53 2000 C 21 80 25 55 30 60 160 1 11 x 10 12 0 20 14 145 120 78 96 64 1600 C 21 80 25 55 45 75 180 1 2 10 x 10 12 0 20 14 145 120 78 96 64 2000 C 21 80 25 55 35 65 170 1 11 x 10 12 0 20 14 147 1 AFU...

Page 8: ...11 x 10 12 0 20 14 130 100 65 80 52 1200 B 17 1 2 80 25 55 40 70 170 1 2 10 x 8 12 0 20 14 125 120 78 96 64 2000 C 21 80 25 55 30 60 160 1 11 x 10 12 0 20 14 150 1 AFUE numbers are determined in accor...

Page 9: ...rrections or resizing of the common venting sys tem must be in accordance with the National Fuel Gas Code ANSI Z223 1 or Section 7 Venting Systems and Air Supply for Appliances CAN CGA B149 1 or 2 Ins...

Page 10: ...eld installation Internal Installation 1 Select desired filter position left right side or bottom Remove the corresponding cabinet cut outs per instruc tions provided 2 Install snap in retainer clips...

Page 11: ...m structure is suitable to support the weight of the furnace Refer to Figure 3 on page10 for unit dimensions and Refer to Table3 on page7 for unit weights Be sure to seal the furnace to plenum connect...

Page 12: ...ort at return air end of unit Units may also be suspended by using straps or other mate rial at the same location All four suspension points must be level to ensure quiet furnace operation DOWNFLOW MO...

Page 13: ...m at test pressures equal to or less than 1 2 psig 3 48 kPa Gas piping may be connected from either side of the furnace Sizing and installation of the supply gas line should comply with the local util...

Page 14: ...e the screw retaining the wiring box Route the power wiring through the unit side panel with a conduit connector or other proper connection Make wiring connections as shown in Figure 11 or 12 Replace...

Page 15: ...the cabinet NOTE Some electronic thermostats do not have adjustable heat anticipators They may have other type cycle rate FIGURE 11 UPFLOW MODELS P DU G8D UH ELECTRICAL WIRING FIGURE 12 DOWNFLOW MODE...

Page 16: ...gh temperature limit control is located on the furnace vestibule panel just to the right and above the gas valve This is an automatic reset control and provides over temperature protection due to redu...

Page 17: ...n off all other gas appliances connected to gas meter 2 With the furnace turned on measure the time needed for one revolution of the hand on the smallest dial on the meter A typical domestic gas meter...

Page 18: ...screw counter clockwise Adjust regulator until pressure shown on manometer matches the pressure specified on the appli ance rating plate 6 Replace low adjustment seal screw and tighten securely Cycle...

Page 19: ...g label and Figure 16 on page19 You may select a heating speed and a cooling speed They may be the same speed or a different speed To use the same speed tap for heating and cooling the heat terminal a...

Page 20: ...aner Connection Two 1 4 spade terminals EAC and EAC N for electronic air cleaner connections are located on the control board The terminals provide 115 VAC 1 0 amp maximum during circu lating blower o...

Page 21: ...1443 1353 1270 1137 993 800 LOW 1377 1297 1284 1271 1246 1194 1125 1005 851 727 120 96 1600 C HIGH 1927 1855 1780 1693 1611 1503 1382 1224 1039 833 MED 1649 1608 1556 1502 1423 1342 1218 1075 910 723...

Page 22: ...64 964 851 725 594 LOW 1024 1018 1002 970 930 882 798 722 622 508 80 64 1600 B HIGH 2047 1992 1911 1842 1780 1688 1607 1513 1412 1284 MED 1862 1826 1764 1698 1629 1558 1496 1408 1310 1177 LOW 1673 165...

Page 23: ...is satisfied the inducer motor is reduced to low speed and the second stage gas valve is de energized upon opening of the second stage pressure switch contacts The circulator remains on high heat spee...

Page 24: ...reinstalling the filter be sure the filter completely covers the cabinet opening and is secured in place by the wire retainer Downflow Installations 1 Turn off electrical power supply to the furnace a...

Page 25: ...e orientation of the burner flanged side down before removing Burners may be cleaned by rinsing in hot water or by using a vacuum cleaner CLEANING THE HEAT EXCHANGER Lower Heat Exchanger Access 1 Turn...

Page 26: ...INUOUS FLASHING 1 sec on 1 sec off This indi cates that flame was sensed when there was not a call for heat With this fault code the control will also turn on both the inducer motor and supply air blo...

Page 27: ...r faulty gas valve LED ON CONSTANTLY This indicated an internal fault in the furnace control discovered during its self check proce dure Replace the control 60 MINUTE AUTOMATIC RESET FROM LOCKOUT This...

Page 28: ...ELECTRICAL 1NP0480 Propane Conversion Kit 1SR0302 External Side Filter Rack 6 Pack 1BR0314 External Bottom Filter Rack Cabinet A 1BR0317 External Bottom Filter Rack Cabinet B 1BR0321 External Bottom F...

Page 29: ...035 14527 000 REV A 599 Form 650 77 N3U Unitary Products Group 29 FIGURE 18 SEQUENCE OF OPERATION...

Page 30: ...035 14527 000 REV A 599 Form 650 77 N3U 30 Unitary Products Group WIRING DIAGRAM UPFLOW HORIZONTAL MODELS P DD G8D UH NOTE The furnace s control system depends on correct polarity of the power supply...

Page 31: ...035 14527 000 REV A 599 Form 650 77 N3U Unitary Products Group 31 WIRING DIAGRAM DOWNFLOW MODELS P DD G8D DN NOTE The furnace s control system depends on correct polarity of the power supply...

Page 32: ...hange without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 650 77 N2U 1198 650 77 N3U 599 Unitary 5005 Interstate Norman Product Drive OK Group North...

Reviews: