background image

035-14527-000 REV A (599)

Form 650.77-N3U

Unitary Products Group

25

4.

Note the wire/terminal location and then remove the 
blower wiring from the furnace control. Remove the pro-
tective boot and disconnect run capacitor wires. Remove 
the screws securing the electrical panel to the blower 
housing. Pull blower assembly out of the unit. When 
cleaning or servicing the blower assembly, DO NOT 
remove or change the balance clips on the blower wheel.

5.

To reassemble, reverse the procedure, restore power to 
the furnace and verify operation.

Downflow Installations

1.

Disconnect the electrical supply to the furnace and 
remove the access doors.

2.

Remove the two wires leading to the auxiliary limit 
mounted on the side opposite the blower motor.

3.

Remove four top panel screws and lift the top panel 
enough to disengage and remove the flue chase assem-
bly.

4.

Remove blower assembly mounting screws and slide the 
blower assembly out of the slots in the deck. If the two 
shipping screws were not previously removed, also 
remove and discard these two screws located on each 
front corner of the blower assembly.

5.

Note the wire/terminal location and then remove the 
blower wiring from the furnace control. Remove the pro-
tective boot and disconnect run capacitor wires. Remove 
the screws securing the electrical panel to the blower 
housing. Pull blower assembly out of the unit. When 
cleaning or servicing the blower assembly, DO NOT 
remove or change the balance clips on the blower wheel.

6.

To reassemble, reverse the procedure, restore power to 
the furnace and verify operation.

Burner Removal/Cleaning

The main burners should be checked periodically for dirt
accumulation.

If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit and turn off gas 
supply at the shutoff valve.

2.

Remove the blower and burner compartment access 
doors.

3.

Unplug ignitor from the wire harness and remove the 
ignitor/bracket assembly from the burner air shield. Han-
dle the ignitor carefully as it is fragile and easily broken.

4.

Note the location and then disconnect the sensor and 
rollout switch wires located on the top of the air shield 
and remove the shield.

5.

Remove the two screws securing each burner to the 
burner assembly. Note the orientation of the burner 
(flanged side down) before removing. Burners may be 

cleaned by rinsing in hot water or by using a vacuum 
cleaner.

CLEANING THE HEAT EXCHANGER

Lower Heat Exchanger Access

1.

Turn off the electrical power to the unit and turn off gas 
supply at the shutoff valve.

2.

Remove the blower and burner compartment access 
doors. Disconnect the gas supply piping at the union to 
permit removal of the entire burner and gas control 
assembly from the vestibule panel. Use the wrench boss 
on the gas valve when removing or installing this piping.

3.

Unplug the ignitor from the wire harness. Disconnect 
sensor and rollout switch wires located on top of the air 
shield. Identify and note the location of all leads for ease 
of reinstallation. Also disconnect the wires at the side 
rollout switches (upflow only) and the gas valve wires.

4.

Remove the screws holding the burner assembly to the 
vestibule panel and remove this assembly. Handle the 
assembly carefully since it contains the ignitor which is 
fragile and easily broken. The lower portion of the heat 
exchanger will now be exposed. To clean the burner 
assembly, use a vacuum cleaner, or remove the burners 
as outlined in burner cleaning, and clean in hot water.

Upper Heat Exchanger Access

1.

Perform steps 1-4 above.

2.

Disconnect vent piping from the vent motor assembly at 
the top panel on the furnace (upflow only). On downflow 
installations this is not necessary.

3.

Unplug the ventor motor wires and ground wire. Remove 
the pressure switch tubing at the tap on the ventor motor 
housing.

NOTE: 

It is recommended that replacement gaskets be avail-

able before removing ventor motor.

4.

Remove six mounting screws that hold the ventor motor 
to the restrictor plate. The surface is gasketed and gas-
ket can be reused if it is carefully removed. It is neces-
sary to remove this assembly to gain access to the 
restrictor plate mounting holes. The assembly may be 
vacuumed if cleaning is necessary. If any vent assembly 
parts are damaged, replace with an entire new assembly 
(except for gaskets).

5.

Remove the perimeter screws attaching the restrictor 
plate assembly to the vestibule panel. The surface is 
also gasketed. The assembly, including the flue baffle 
plate (rear) may be vacuumed or cleaned with hot water 
if necessary.

6.

The upper portion of the heat exchanger is now accessi-
ble. With a long flexible wire brush, clean inside each 
tube at both the top and bottom. The brush must pass 

Summary of Contents for P*DD & G8D-DN series

Page 1: ...MID EFFICIENCY GAS FIRED TUBULAR HEAT EXCHANGER SERIES MODELS P DU G8D UH Upflow Horizontal P DD G8D DN Downflow 57 120 MBH INPUT 035 14527 000 REV A 599 Form 650 77 N3U FOR YOUR SAFETY WHAT TO DO IF...

Page 2: ...ds 4 Paper bags boxes or other paper products Never operate the furnace with the blower door removed To do so could result in serious personal injury and or equipment damage CONTENTS GENERAL INFORMATI...

Page 3: ...arify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment or property damage may occur if ins...

Page 4: ...appliance when access is required for servicing and cleaning Eighteen 18 inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue ve...

Page 5: ...of all appliances located in the space NOTE Ducts must have the same cross sectional area as the free area in the opening to which they are connected The minimum dimension of rectangular ducts shall b...

Page 6: ...inting inks paint removers varnishes etc o Hydrochloric acids p Cements and glues q Antistatic fabric softeners for clothes dryers r Masonry acid washing chemicals VENTING CATEGORY I VERTICAL VENTING...

Page 7: ...0 53 2000 C 21 80 25 55 30 60 160 1 11 x 10 12 0 20 14 145 120 78 96 64 1600 C 21 80 25 55 45 75 180 1 2 10 x 10 12 0 20 14 145 120 78 96 64 2000 C 21 80 25 55 35 65 170 1 11 x 10 12 0 20 14 147 1 AFU...

Page 8: ...11 x 10 12 0 20 14 130 100 65 80 52 1200 B 17 1 2 80 25 55 40 70 170 1 2 10 x 8 12 0 20 14 125 120 78 96 64 2000 C 21 80 25 55 30 60 160 1 11 x 10 12 0 20 14 150 1 AFUE numbers are determined in accor...

Page 9: ...rrections or resizing of the common venting sys tem must be in accordance with the National Fuel Gas Code ANSI Z223 1 or Section 7 Venting Systems and Air Supply for Appliances CAN CGA B149 1 or 2 Ins...

Page 10: ...eld installation Internal Installation 1 Select desired filter position left right side or bottom Remove the corresponding cabinet cut outs per instruc tions provided 2 Install snap in retainer clips...

Page 11: ...m structure is suitable to support the weight of the furnace Refer to Figure 3 on page10 for unit dimensions and Refer to Table3 on page7 for unit weights Be sure to seal the furnace to plenum connect...

Page 12: ...ort at return air end of unit Units may also be suspended by using straps or other mate rial at the same location All four suspension points must be level to ensure quiet furnace operation DOWNFLOW MO...

Page 13: ...m at test pressures equal to or less than 1 2 psig 3 48 kPa Gas piping may be connected from either side of the furnace Sizing and installation of the supply gas line should comply with the local util...

Page 14: ...e the screw retaining the wiring box Route the power wiring through the unit side panel with a conduit connector or other proper connection Make wiring connections as shown in Figure 11 or 12 Replace...

Page 15: ...the cabinet NOTE Some electronic thermostats do not have adjustable heat anticipators They may have other type cycle rate FIGURE 11 UPFLOW MODELS P DU G8D UH ELECTRICAL WIRING FIGURE 12 DOWNFLOW MODE...

Page 16: ...gh temperature limit control is located on the furnace vestibule panel just to the right and above the gas valve This is an automatic reset control and provides over temperature protection due to redu...

Page 17: ...n off all other gas appliances connected to gas meter 2 With the furnace turned on measure the time needed for one revolution of the hand on the smallest dial on the meter A typical domestic gas meter...

Page 18: ...screw counter clockwise Adjust regulator until pressure shown on manometer matches the pressure specified on the appli ance rating plate 6 Replace low adjustment seal screw and tighten securely Cycle...

Page 19: ...g label and Figure 16 on page19 You may select a heating speed and a cooling speed They may be the same speed or a different speed To use the same speed tap for heating and cooling the heat terminal a...

Page 20: ...aner Connection Two 1 4 spade terminals EAC and EAC N for electronic air cleaner connections are located on the control board The terminals provide 115 VAC 1 0 amp maximum during circu lating blower o...

Page 21: ...1443 1353 1270 1137 993 800 LOW 1377 1297 1284 1271 1246 1194 1125 1005 851 727 120 96 1600 C HIGH 1927 1855 1780 1693 1611 1503 1382 1224 1039 833 MED 1649 1608 1556 1502 1423 1342 1218 1075 910 723...

Page 22: ...64 964 851 725 594 LOW 1024 1018 1002 970 930 882 798 722 622 508 80 64 1600 B HIGH 2047 1992 1911 1842 1780 1688 1607 1513 1412 1284 MED 1862 1826 1764 1698 1629 1558 1496 1408 1310 1177 LOW 1673 165...

Page 23: ...is satisfied the inducer motor is reduced to low speed and the second stage gas valve is de energized upon opening of the second stage pressure switch contacts The circulator remains on high heat spee...

Page 24: ...reinstalling the filter be sure the filter completely covers the cabinet opening and is secured in place by the wire retainer Downflow Installations 1 Turn off electrical power supply to the furnace a...

Page 25: ...e orientation of the burner flanged side down before removing Burners may be cleaned by rinsing in hot water or by using a vacuum cleaner CLEANING THE HEAT EXCHANGER Lower Heat Exchanger Access 1 Turn...

Page 26: ...INUOUS FLASHING 1 sec on 1 sec off This indi cates that flame was sensed when there was not a call for heat With this fault code the control will also turn on both the inducer motor and supply air blo...

Page 27: ...r faulty gas valve LED ON CONSTANTLY This indicated an internal fault in the furnace control discovered during its self check proce dure Replace the control 60 MINUTE AUTOMATIC RESET FROM LOCKOUT This...

Page 28: ...ELECTRICAL 1NP0480 Propane Conversion Kit 1SR0302 External Side Filter Rack 6 Pack 1BR0314 External Bottom Filter Rack Cabinet A 1BR0317 External Bottom Filter Rack Cabinet B 1BR0321 External Bottom F...

Page 29: ...035 14527 000 REV A 599 Form 650 77 N3U Unitary Products Group 29 FIGURE 18 SEQUENCE OF OPERATION...

Page 30: ...035 14527 000 REV A 599 Form 650 77 N3U 30 Unitary Products Group WIRING DIAGRAM UPFLOW HORIZONTAL MODELS P DD G8D UH NOTE The furnace s control system depends on correct polarity of the power supply...

Page 31: ...035 14527 000 REV A 599 Form 650 77 N3U Unitary Products Group 31 WIRING DIAGRAM DOWNFLOW MODELS P DD G8D DN NOTE The furnace s control system depends on correct polarity of the power supply...

Page 32: ...hange without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 650 77 N2U 1198 650 77 N3U 599 Unitary 5005 Interstate Norman Product Drive OK Group North...

Reviews: