LION microPLC
▪
Maintenance – Software
43
12
Maintenance
–
Software
12.1
Update Firmware (ProConOS)
12.1.1
Procedure via FTP upload
With this procedure following files can be updated via FTP upload, if needed:
▪ Firmware.fw
▪ BtldrCfg.ini
Do not disconnect the power supply
from the device during the entire
firmware update process, this can cause permanent damage.
The firmware update process deletes the application.
Firmware updates are only possible with
HW revision F
and newer, and
firmware version 1.6
and newer.
For a downgrade please contact Lütze Transportation GmbH.
For a firmware update the two files "
Firmware.fw
" + "
BtldrCfg.ini
" are required.
You can get this from Lütze Transportation GmbH.
Please contact us, see chapter “Service” on page 55.
The files are only transferred if a restart is done, after the copy procedure.
A change of the files is only accept after a restart.
It may be necessary to release the TotalComander via firewall.
1. Connect the microPLC with an
ethernet cable to your computer.
2. Open the
Total Commander
.
A new window opens, where you can
see all files
3. Connect the microPLC with the file
manager via FTP client.
You can only use the FTP client to drag files between your computer and
the microPLC.