5 Control and reference input
DE
EN
* - Only if 280-RSSL1=(7) TBSEL
** - Only if 651-CDSSL=(6) OPTN2
*** - Only if 166-UDSSL=(3) OPTN2
Control word
Status word
Bit
Function
Signal
Bit
Function
Signal
0
Activate
0
Ready for start
1
Disable power
1
On
2
Emergency stop
1 = Emergency stop
2
Enable operation
3
Enable operation
3
Fault
4
FFTB0, select table ref-
erence (significance 2
0
) *
4
Power disabled
1 = Voltage disabled,
function not implemented
5
FFTB1, select table ref-
erence (significance 2
1
) *
Binary selection of a table
reference
1)
5
Emergency stop
6
FFTB2, select table ref-
erence (significance 2
2
) *
6
Switch-on inhibit
7
Reset fault
0->1 = Reset latest device
error
4)
7
Warning
1 = Warning delivered
8
CUSEL, data selection ** 0 = Characteristic data set 1,
1 = Characteristic data set 2
2)
8
CAN status
0 = System Stop
1 = System Start
9
UM0, select user mode
(significance 2
0
) ***
Binary selection of active user
mode
3)
9
Remote
1 = Parameter setting
possible
10
UM1, select user mode
(significance 2
1
) ***
10
Reference reached
1 = Reference reached
11
Vacant
Vacant
11
Limit value
1 = Fmin Fmax limitation
active
12 Vacant
Vacant
12 Status of input ISD03
Status of input ISD03
13
Reference status OSD02
if 242-FOS02=OPTN2
1 = Output OSD02 = high
13
Status of input ISD02
Status of input ISD02
14
Reference status OSD01
if 241-FOS01=OPTN2
1 = Output OSD01 = high
14
Status of input ISD01
Status of input ISD01
15
Reference status OSD00
if 240-FOS00=OPTN2
1 = Output OSD00 = high
15
Status of input ISD00
Status of input ISD00
Table 5.3
DRIVECOM control word and status word
Summary of Contents for CM-CAN1
Page 8: ...User Manual CM CAN1...
Page 28: ...3 6 User Manual CM CAN1 3 Commissioning and configuration...
Page 50: ...4 22 User Manual CM CAN1 4 Setting the device parameters...
Page 72: ...6 8 User Manual CM CAN1 6 Fault rectification...
Page 78: ...7 6 User Manual CM CAN1 7 Examples...
Page 83: ......