User Manual CM-CAN1
4-11
4 Setting the device parameters
DE
EN
573-CACTR - Control word
The control word received via the control identifier is entered in parameter
573-CACTR. During commissioning the parameter can be used to check
the reception of data. The parameter is for display purposes only.
572-CASTA - Status word
The status of the preset state machine is entered in parameter 572
CASTA. The data content of the parameter corresponds to data bytes 0
and 1 in the status identifier. The parameter is for display purposes only.
288-FOPT2 - Reference from option slot 2
The reference value received via the control identifier is entered in param-
eter FOPTx. The data content of the parameter corresponds to data bytes
2-5 of the control identifier. The interpretation of the value is dependent
on the selected operation mode. The parameter is for display purposes
only.
4.3.3 Data backup
150-SAVE - Back-up device setup
Parameter to back-up the complete device setup to the Flash memory. All
parameters are first held in the RAM. So that the parameters are available
again after power-off, they must be backed-up. To do so, parameter
150-SAVE is set to 1 after all other parameters have been set. The save
operation takes a few hundred milliseconds. During that time the drive
Subject area
Value range
Factory set.
Unit
Data type
Memory type
_57OP
0000H ... FFFFH
0000H
–
USIGN16
RAM actual
value
Subject area
Value range
Factory set.
Unit
Data type
Memory type
_57OP
0000H ... FFFFH
0000H
–
USIGN16
RAM actual
value
Subject area
Value range
Factory set.
Unit
Data type
Memory type
_28RS
-32764 ... 32764
0
Hz
INT32Q16
RAM actual
value
Summary of Contents for CM-CAN1
Page 8: ...User Manual CM CAN1...
Page 28: ...3 6 User Manual CM CAN1 3 Commissioning and configuration...
Page 50: ...4 22 User Manual CM CAN1 4 Setting the device parameters...
Page 72: ...6 8 User Manual CM CAN1 6 Fault rectification...
Page 78: ...7 6 User Manual CM CAN1 7 Examples...
Page 83: ......