How to Program the Unit
Site Number
Subnet
Unit Number
Site codes separate one site from another. The site is the area covered by
all the Alertex units on one system. Choose a number between 1 and 32
and set this on all units in the system. Nearby units will be detected by
the system but as long as they are on a different site code, they cannot
active your system.
Currently Alertex is set to default subnet 1. This is a future feature which
is not currently used and should be left on the default setting.
Unit numbers identify individual Alertex units on the site. There are 64
unit numbers available which is the maximum number of Alertex units per
site. If an IP Masthead is used with the system then this must have the
Name
Range
Default
Description
SI
1 - 32
1
Site Number
SU
1 - 8
1
Subnet Number
Un
1 - 64
1
Unit Number
Cr
0 / 1
0
Call Repeater:
1 = Enabled, 0 = Disabled
CP
3 - 99
99
Call Period: Value increases in 1
minute increments up to 50 minutes.
After 50 minutes, value increases in 5
minute increments, ie. 55, 60, 65, etc.
MU
0 / 1
0
Master Unit:
1 = Enabled, 0 = Disabled
SP
0 / 1
1
Serial Port:
1 = Enabled, 0 = Disabled (not used)
ts
0 - 30
10
Time Set: Values in minutes
(0 means infinite)