Table 36
Address
range
alue type
Description
4000 - 4127
integer
(16 bits)
The value is located in the 16-bit register
4300 - 4325
integer
(16 bits)
The value is located in the 16-bit register
4400 - 4439
integer
(16 bits)
The value is located in the 16-bit register
4500 - 4764
integer
(16 bits)
The value is located in the 16-bit register
6000-6075
float
(32 bits)
The value is located in two following 16-bit regi-
sters. Registers contain the same data as 32-bit
registers from the area 7500-7537. Registers are
readout type only. Byte order (B1, B0, B3, B2)
7000 -7075
float
(32 bits)
The value is located in two following 16-bit regi-
sters. Registers contain the same data as 32-bit
registers from the area 7500-7537. Registers are
readout type only. Byte order (B3, B2, B1, B0)
6200-6337
float
(32 bits)
The value is located in two following 16-bit regi-
sters. Registers contain the same data as 32-bit
registers from the area 7600-7719. Registers can
be read and written. Byte order (B1, B0, B3, B2)
7200-7337
float
(32 bits)
The value is located in two following 16-bit regi-
sters. Registers contain the same data as 32-bit
registers from the area 7600-7719. Registers can
be read and written. Byte order (B3, B2, B1, B0)
7500-7537
float
(32 bits)
The value is located in the 32-bit register. Regi-
sters contain measured and calculated data by
the transducer. Registers are readout type only.
Byte order (B3, B2, B1, B0)