Fig.29. Method of connecting the RS-485 interface
Computer
Transducer P30
Transducer P30
Transducer P30
The PC card transmission line marking depends on the card
manufacturer.
5. .2. MODBUS protocol description
The implemented protocol complies with Modicon’s PI-MBUS-
300 Rev G specification. P30U MODBUS protocol serial interface para-
meters :
Transducer address 1..247.
Transmission rate: 4800, 9600, 19200, 38400, 57600, 115200,
230400, 256000 [b/s].
Operation mode: RTU with the frame format: 8n2, 8e1, 8o1, 8n1.
Maximum time to start response: 200 ms (the response time may
get longer up to 500ms during saving the data to the SD/SDHC
card).
Serial interface configuration consists of setting the transmis-
sion rate, device address and the information unit format – protocol.
•
•
•
•