Lucent Technologies Lineage
®
2000 25A Ferroresonant Rectifier J85502A-1
8 - 6 Spare Parts and Replacement Procedures
Issue 4 May 1998
14. Replace the two mounting nuts and associated lockwashers
securing CM1.
15. Replace the header connectors on CM1.
16. Replace the four quick-disconnect connectors on CM1.
17. Reconnect all cables that were disconnected in Step 8.
18. If the rectifier is to be restored to service, refer to
“Restoring a Rectifier to Service” in Section 7.
Replacing CM2
Control Board
Follow instructions in “Handling Circuit Modules” to minimize
electrostatic discharge when handling circuit modules.
1. Turn the rectifier POWER switch Off.
2. Turn the rectifier (CBA1) DC OUTPUT circuit breaker
Off (down).
3. At the ac service panel supplying power to the rectifier,
remove the input fuses assigned to the rectifier, or turn the
circuit breaker Off.
4. At the plant controller, remove the REG fuse associated
with the rectifier.
5. At the rectifier, loosen the locking screws and open the
rectifier door.
6. Locate the CM2 control board.
7. Disconnect J2A from CM2 by unlatching first, then
pulling the cable connector.
8. Disconnect the J1A connector on the cable from the CM1
option board.
Caution
Support the CM2 control board with your hands when
connecting and disconnecting the cables, or damage to the
board may result.
Do NOT disconnect cables by pulling the cable.