Lucent Technologies Lineage
®
2000 25A Ferroresonant Rectifier J85502A-1
Issue 4 May 1998
Product Description 2 - 7
•
The digital output meter is optional on the J85502A-1
rectifier. The meter displays (1) the rectifier output current
when the selector switch is in the AMPS position, (2) the
rectifier output voltage when the selector switch is in the
RECT V position, and (3) the plant battery voltage when
the selector switch is in the BATT V position. The default
display is rectifier output current. Table 2-A gives the
accuracy of this meter in the various positions. The
accuracy of the reading depends on the vintage of the digital
meter board (CM3) in the rectifier. The POWER (control)
Figure 2-1: Control Panel of J85502A-1 Rectifier
Table 2-A: Digital Meter Accuracy
Meter Position
Accuracy
RECT V
±0.5 volt for Series 1 or 2 CM3 digital meter
boards
±0.02 volt for Series 3 CM3 digital meter
boards*
BATT V
±0.02 volt for any CM3 digital meter board
AMPS
±2.5 percent of rectifier rating
*Series 3 CM3 boards can be identified by the designation
“AM3” stamped on the wiring (noncomponent) side of the
board. See Figure 7-1 for a partial sketch of CM3 boards.
OUTPUT
RECT V
BATT V
AMPS
OUTPUT
VOLTS ADJ
DC
OUTPUT
REG
POWER
ON
RFA
ALARM
RECT
TEST
FL
NL
OFF
1/2 AMP
+
–