Lucent Technologies Lineage
®
2000 25A Ferroresonant Rectifier J85502A-1
5 - 8 Installation
Issue 4 May 1998
on TB3 in the rectifier. DC return (ground) is positive for
negative output voltage plants, and negative for positive
output voltage plants. Torque connection to 30 in-lb.
7. Remove tape or insulation from connector at other end of
cable and terminate on plant ground bus bar.
8. Place dc output cable in cable rack.
9. Thread end of output cable through right side of rectifier
and attach connector to the remaining terminal on TB3 in
rectifier (negative terminal for negative output, positive
terminal for positive output). Torque to 30 in-lb.
10. Remove tape or insulation from connector at other end of
output cable, and terminate connector on plant charge bus
bar.
Installing Plant
Control Cable
Assembly for a
Lucent
Technologies
Controller
The Plant Control Cable Assembly has a 24-pin or 16-pin
connector on one end and a 40-pin connector on the other end.
The 24-pin or 16-pin end terminates on the battery plant
controller and the 40-pin end terminates on connector P2A of the
CM2 control board located in the rectifier.
Use Figures 5-1 and 5-2 as references for this section.
1. Route the plant control cable from the controller via the
cable racks to the rectifier and through the opening
provided for this cable in the right side of the unit.
2. Terminate the 40-pin connector on P2A of CM2 and dress
cable (using strain relief bushings and cable ties provided)
inside the rectifier, allowing for the door to be opened and
closed without putting stress on the cable. After securing
the cable, disconnect the cable from P2A.
3. Determine the number to be assigned to the rectifier in the
rectifier lineup, that is, 1, 2, 3, etc.
Warning
Avoid arc or sparks. Before making contact between
connectors and the output bus bar in the next step, use a digital
multimeter (DMM) to verify a true open circuit between
connector and known battery plant ground.