Chapter 6 High-speed Link Service
6-7
(2) Communication Module Settings and Communication period settings
Double-click one of the High-speed links 01~12 on the [Fig.6.4.3] screen to open the
Communication Module setting dialog box depicted in [Fig. 6.4.4] to setup communication
module and communication period.
[Fig. 6.4.4] Communication module setting
Set the applicable communication module and communication period in the dialog box.
Item
Description
Communication
module settings
Module type
Select the installed communication module type.
Base No.
Select the base number where applicable FEnet module is installed.
Slot No.
Select the slot number where applicable FEnet module is installed.
Communication
period settings
Period type
- High-speed link service is used to send and receive data by user
defined parameters when the execution of PLC program is ended.
Thus, if the scan time of PLC program is as short as
㎳
or less,
the communication data will be increased since the
communication module sends data at the end of every scan, which
will cause decreased efficiency of the whole communication
system. In order to prevent this, the communication is controlled
by the specified communication period whose setting range is 20
㎳
~ 10sec, which will be automatically set to default of 200
㎳
if
not specified.
- The communication period will be applied for Send blocks.
- The communication period will be applied identically to all the Send
blocks included in the same High-speed link parameter number.