Chapter 5 XG5000 Program
5-11
[Fig. 5.2.13] Standard settings (details) in case of XGR
Details on the screen displayed in [Fig. 5.2.13] are as follows;
Among those details below, IP address, High-speed link station No. and media shall be reset
appropriately for the application environment.
1) TCP/IP setting (XGI/XGK series)
Classification
Description
ONE IP
Solution
1. You are able to connect to master base FEnet of XGR redundancy system with one
IP regardless of Master conversion. For this, in case of master conversion, FEnet
modules of master base and standby base exchange each other’s IP address
2. If you check ONE IP Solution, ONE IP Solution function is activated and you
register only one IP
3. When using ONE IP Solution, IP address should be even number. That number
become FEnet module IP address of master base
4. The above 1 becomes FEnet module IP address of standby base
High-speed link
station No.
Specify station No. for High-speed link communication between LSIS PLCs’ FEnet I/F
modules, which shall not be duplicated identically to the correspondent
communication module.
Media
Select media to use.
AUTO (electric) : automatically detects the module presently installed.
10M/HALF : 10MBps Half Duplex electric
10M/FULL : 10MBps Full Duplex electric
100M/HALF : 100MBps Half Duplex electric
100M/FULL : 10MBps Full Duplex electric
FX/100M/HALF : 100MBps Half Duplex optical
FX/100M/FULL : 100MBps Full Duplex optical
IP address
Specify the IP Address of the applicable FEnet I/F module.