Chapter 2 Specification
2-1
Chapter 2 Specification
2.1 General Specification
The general specification of XGT series is as follows.
No.
Items
Specifications
Related standards
1
Ambient
temperature
0 ~ 55
°
C
2
Storage
temperature
−
25 ~
+
70
°
C
3
Ambient
humidity
5 ~ 95%RH (Non-condensing)
4
Storage humidity
5 ~ 95%RH (Non-condensing)
5
Vibration
resistance
Occasional vibration
-
Frequency
Acceleration
Amplitude
How many times
IEC61131-2
5
≤f< 8.4
㎐
-
3.5mm
10 times each
directions
(X, Y and Z)
8.4
≤f≤150
㎐
9.8
㎨
-
Continuous vibration
Frequency
Acceleration
Amplitude
5
≤f< 8.4
㎐
-
1.75mm
8.4
≤f≤150
㎐
4.9
㎨
(0.5G)
-
6
Shock
resistance
•
Peak acceleration: 147 m/s
2
(15G)
•
Duration: 11ms
•
Half-sine, 3 times each direction per each axis
IEC61131-2
7
Noise resistance
Square wave
Impulse noise
AC:
±
1,500 V
DC:
±
900 V
LSIS standard
Electrostatic discharge
4kV (Contact discharge)
IEC61131-2
IEC61000-1-2
Radiated electromagnetic field noise
80 ~ 1,000 MHz, 10V/m
IEC61131-2,
IEC61000-1-3
Fast transient/bust
noise
Segment
Power supply
module
Digital/analog input/output
communication interface
IEC61131-2
IEC61000-1-4
Voltage
2kV
1kV
8
Environment
Free from corrosive gasses and excessive dust
9
Altitude
Up to 2,000 m
10
Pollution
degree
Less than equal to 2
11
Cooling
Air-cooling
Notice
1) IEC (International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic field, publishes international standards and manages applicable estimation system related with.
2) Pollution degree:
An index indicating pollution degree of the operating environment which decides insulation performance of the devices. For instance, Pollution
degree 2 indicates the state generally that only non-conductive pollution occurs. However, this state contains temporary conduction due to dew
produced.
Summary of Contents for XBL-EIPT
Page 53: ...Chapter 5 Installation of Software and communication Parameters 5 18 ...
Page 98: ...Chapter 7 Diagnosis Function 7 11 Figure 7 3 4 FlashArea Log Screen of System Log ...
Page 106: ...Chapter 7 Diagnosis Function 7 19 Fig 7 4 9 Remote 2 connection directly via Ethernet ...
Page 119: ...Appendix A 12 A 3 External Dimension Dimension Unit mm XBL EIPT ...