Chapter 3 Installation and Test Operation
3-13
(2) Using XGI CPU
(a) Basic system configuration
Classification
XGI-CPUU
Max. extension stage
7 stages
Max. number of I/O
module extension
mounted
96 moduls
Max. I/O contact
number
16 points module : 1,536 points
32 points module : 3,072 points
64 points module : 6,144 points
Max. extension distance
15m
I/O number is constantly allocated to 64 points per slot of the base.
Each slot of the base is allocated with 64 points, irrespectively of module mounted or its type.
The position on which a special module is mounted or the number is not limited.
Unlike digital I/O module, a special module is not allocated for any constant I/O number.
A special module is controlled by the exclusive function block and automatically allocated for
the memory.
For instance, the I/O number of 12 slot base is allocated as follows.
Remark
1) The basis base has its base number as „0‟ and the extension base has a switch to set the base number.
2) Operation starts as long as the module type set as I/O parameter and the actually mounted module type coincide.
%QX 0.11.0 ~ 31
%QX 0.10.0 ~ 31
%QX 0.9.0 ~ 15
%IX 0.8.0 ~ 31
Po
wer
I
1
6
I
1
6
I
3
2
I
6
4
O
1
6
O
3
2
O
3
2
O
6
4
I
3
2
O
3
2
O
1
6
O
3
2
C
P
U
Base no. 1
Slot
no.
0 1 2 3 4 5 6 7 8 9 10
11