![LS Industrial Systems iG5A Series Manual Download Page 95](http://html1.mh-extra.com/html/ls-industrial-systems/ig5a-series/ig5a-series_manual_1943816095.webp)
Chapter 7. Inverter Parameter
83
Chapter 7. Inverter Parameter
7.1 Related Parameter List
Code
Name of
Parameter
Default
Range
Description
drv
Drive Mode
1. Fx/Rx-
1
0. Keypad
To command Inverter run
with CANopen, it requires
setting as 4. FieldBus
1. Fx/Rx-1
2. Fx/Rx-2
3. RS485
4. FieldBus
Frq
Frequency
setting
method
0.
Keypad-1
0. Keypad-1
To command Inverter
frequency with CANopen,
it requires setting as
9. FieldBus
1. Keypad-2
2. -10~10V
3. 0~10V
4. 0~20mA
5. "2" + "4"
6. "3" + "4"
7. RS485
8. Digital
Volume
9. FieldBus
10. Pulse
C 1
FieldBus
Option
Name
-
-
When iG5A CANopen
communication module is
installed,
it indicates
“CAn”.
C 2
FBus S/W
Ver
-
-
Indicates the version of
CANopen communication
module
C 3
FBus ID
1
1 ~ 127
Inverter ID to be set.
C 4
FBus
BaudRate
1Mbps
1Mbps
Requires setting at
Baudrate used in the
network with which
inverter is connected.
800Kbps
500Kbps
250Kbps
125Kbps