Chapter 6. Profile
78
As shown in the figure, the deceleration time is determined using the Delta
speed and Delta time. For the safety of the inverter, the delta_speed was
fixed to Max speed, and the setting parameter was removed.
6.1.3 SDO for IG5A
▶
SDO address in the keypad parameter area
The Keypad parameters are indexed by group. The SubIndex is the code
number.
The table below presents the index values by Group.
Index
Area
0x4010
Drive Group
0x4011
Function Group1
0x4012
Function Group2
0x4013
I/O Group
0x4014
Comm Group
E.g.) To obtain the value of the Output Current which is the Code 8
parameter in Group, read the values in the Index 0x4010 and
SubIndex 0x9