Chapter 7 Maintenance
7-1
Chapter 7 Maintenance
To keep the XGT Panel best, examine the XGT Panel.
7.1 Maintenance
Because an error may be developed by environment, the periodic maintenance is needed. You should check the following
categories once or twice every 6 months.
Maintenance category
Criterion
Action
Power
Within the power change range
(Within
15% / +10%)
Modify the source of electric power in order to be in
the fluctuation range of a permissible voltage.
Environment
Operating
temperature
0 ~ + 50
℃
Modify the operating temperature and humidity to be
proper.
Operating
humidity
10 ~ 85%RH
Vibration
No vibration
Use the anti-vibration rubber and make a count
measure.
Getting loose of power terminal There is no unwinding
Screw the unwound terminal.
Getting loose of
communication connector
There is no unwinding
Screw the unwound terminal.
Reserved part
Amount of reserved part and
reservation
Check the status
Refill the insufficiency and improve the reservation.
Gasket installation status
No gap between the gasket and
panel.
Replace gasket or affix brackets firmly
Gasket status
No damage or deterioration
Replace gasket
Front Panel status check
No damage or deterioration
Use a dry cloth to remove dust and foreign matter.
7.2 Daily Maintenance
Check the followings daily.
Maintenance category
Maintenance contents
Criterion
Action
Mounting status
Check the brackets
Should be mounted firmly
Retighten screws
Power terminal status
Loose terminal screws
Not loose
Retighten screws
Reduce the distance between
compressed terminals.
Keep the proper distance.
Correction
Communication connector
status
Unwinding of fixed screw
Not loose
Retighten screws
Indication LED
Check the lighting
Blue LED should be turned on
Refer to the Appendix 1.
Touch panel surface state
Check the touch panel
No pollution such as water drops or
oil
Surface wiping
Summary of Contents for iXP2 Series
Page 1: ...Human Machine Interface XGT PANEL iXP2 Series ...
Page 51: ...Chapter 5 XGT Panel Menu Explanation 5 14 ...
Page 127: ...Appendix2 Dimensions APP2 1 Appendix 2 Dimensions Unit mm 1 iXP2 08xxA D ...
Page 128: ...Appendix2 Dimensions APP2 2 2 iXP2 10xxA D ...
Page 129: ...Appendix2 Dimensions APP2 3 3 iXP2 12xxA D ...