Chapter 4. Installation and Wiring
4-7
4.2 Wiring
Describes the wiring matters when installing the XGT Panel.
4.2.1
Power Wiring
XGT Panel is divided into DC (DC) and AC (AC) products.
power
Product Name
DC 24V
iXP2-08xxD
iXP2-10xxD
iXP2-12xxD
iXP2-15xxD
AC100-240V
iXP2-08xxA
iXP2-10xxA
iXP2-12xxA
iXP2-15xxA
►
Connecting AC power to a device that uses DC power may cause product damage or fire.
Be careful of connection.
►
'XXD' is a product using DC 24V and 'XXA' is a product using AC100-240.
Be sure to check the polarity of the back of the product before use.
►
The equipment shall be installed in an enclosure which maintains an ingress protection rating protection
rating of at least IP64 and meets the enclosure requirements of IEC 60079-0 and IEC 60079-15, IEC
60079-31.
►
Transient protection shall be provided that is set at a level not exceeding 140 % of the peak rated voltage
value at the supply terminals to the equipment.
►
The equipment shall only be used in an area of not more than pollution degree 2, as defined in
IEC 60664-1.
►
Plugs and sockets shall not be separated while an explosive atmosphere may be present.
►
The equipment presents a potential electrostatic hazard. Clean only with a damp cloth.
► Install in a vertical direction only.
Caution