P05.1.01
– Serial address (node) for the communication protocol.
P05.1.02
– Communication port bit-rate.
P05.1.03
– Data format. 7 bit setting position for ASCII protocol only.
P05.1.04
– Number of stop bits.
P05.1.05
– Communication protocol selection.
P05.1.06, P05.1.07, P05.1.08
– TCP/IP details for applications with Ethernet interface. Not used with other communication module types.
P05.1.09
– Gateway function enable.
M05 – COMMUNICATION UoM Default Range
P05.1.01 Serial node address 01 01-255
P05.1.02 Serial speed bps 9600 1200
2400
4800
9600
19200
38400
P05.1.03 Data format 8 bit – n 8 bit, no parity
8 bit,odd
8 bit, even
7 bit, odd
7 bit, even
P05.1.04 Stop bits 1 1-2
P05.1.05 Protocol Modbus-RTU Modbus-RTU
Modbus-ASCII
Modbus-TCP
P05.1.06 IP address 000.000.000.000 000.000.000.000 -
255.255.255.255
P05.1.07 Subnet mask 000.000.000.000 000.000.000.000 -
255.255.255.255
P05.1.08 IP port 1001 0-9999
P05.1.09 Gateway function OFF OFF/ON
P06.01…P06.06
– Enables or disables the corresponding alarm.
Note:
the use of the auxiliary feedback contact on the IS is recommended even in applications where the backup device is not used. If not even the feedback contact is used however, it will be necessary to deactivate
alarms A02 and A03 by setting P06.02 and P06.03 to OFF.
M06 – ALARMS Default Range
P06.01 Alarm A01 enable ON ON - OFF
P06.02 Alarm A02 enable ON ON - OFF
P06.03 Alarm A03 enable ON ON - OFF
P06.04 Alarm A04 enable ON ON - OFF
P06.05 Alarm A05 enable ON ON - OFF
P06.06 Alarm A06 enable ON ON - OFF
COMMANDS MENU
– The Commands Menu is used to perform occasional operations, like resetting measurements, counters, alarms, etc.
– If the Advanced-level access password was entered, the Commands Menu can also be used to perform automatic operations useful for configuring the instrument.
– The following table shows the functions which are available with the Commands Menu, divided according to the required access level.
CODE
COMMAND
ACCESS
DESCRIPTION
LEVEL
C.01
RESET HI-LO
User / Advanced
Resets the HI and LO values of all measurements
C.02
RESET TRIP COUNTERS
User / Advanced
Resets the trip counters
C.03
RESET PARTIAL ENERGY METERS
User / Advanced
Resets partial energy meters
C.11
RESET TOTAL ENERGY METER
Advanced
Resets total and partial energy meters and tariffs
C.12
PARAMETERS TO DEFAULT P
≤
50kW
Advanced
Restores all settings to factory default values for plants with P
≤
50kW
C.13
PARAMETERS TO DEFAULT P>50kW
Advanced
Restores all settings to factory default values for plants with P>50kW
C.14
PARAMETER BACKUP
Advanced
Saves a backup copy of the settings
C.15
PARAMETERS RESTORE
Advanced
Reloads the settings from the backup copy
C.16
INHIBITION U> UMAX
Advanced
Temporarily disables U> for U>> threshold test
U> threshold enables after 1 hour time or a device reboot
C.17
INHIBITION U< UMIN
Advanced
Temporarily disables U< for U<< threshold test
U< threshold enables after 1 hour time or a device reboot
C.18
RESET EVENT LOG
Advanced
Reset the event log