– For many pages, the
✔
button permits access to sub-pages (for example, to display the maximum and minimum values recorded).
– The sub-page displayed currently is indicated at the bottom left by one of the following icons:
•
IN = Instantaneous value
– Current instantaneous value of the measurement, displayed by default every time the page is changed.
•
HI = Maximum instantaneous value
– Highest value measured by the IP for the corresponding measurement. HIGH values are stored and preserved even in the absence of a power supply. They can be reset
through a dedicated command (see COMMANDS MENU).
•
AV = Average value
– Average value of the measurements, with slowed variations (average of the last minute).
•
LO = Minimum instantaneous value
– Lowest value measured by the IP from the moment voltage is applied. It is reset with the same command used for the HI values.
•
GR = Graphic bars
– Display of measurements through graphic bars.
– The user can specify the page and sub-page to return to automatically after no buttons have been pressed for a given time.
– It is also possible to program PMVF 80 so that the display always remains that which was last selected.
– For the setup of these functions, see MENU M02 – UTILITY.
TABLE OF DISPLAY PAGES
No. Selection via
s
and
t
Selection via
✔
PAGES SUB-PAGES
1
VOLTAGES, FREQUENCY
HI LO AV GR
V(L1-L2), V(L2-L3), V(L3-L1), F(Hz)
2
IP STATE SYNOPTIC
STATE OF IS/BACKUP CONTROL OUTPUTS, FEEDBACK INPUT, R.O.C.O.F/VECTOR SHIFT INHIBIT INPUT,
IP DISABLING INPUT, REMOTE TRIPPING
3
ACTIVE THRESHOLDS – DELAYS IN USE
FREQUENCY THRESHOLDS AND DELAYS CURRENTLY ACTIVE
VOLTAGE THRESHOLDS AND DELAYS CURRENTLY ACTIVE
R.O.C.O.F – VECTOR SHIFT
4
IP TRIP COUNTER
IS TRIP CNT, BACKUP TRIP CNT, REMOTE TRIP CNT, POWER-ON CNT, IS OFF TIME
5
VOLTAGE THRESHOLD TRIP COUNTERS
U>>, U>, U<, U<< CNT
6
FREQUENCY THRESHOLD TRIP COUNTERS
f>>, f>, f<, f<<, R.O.C.O.F TRIP, VECTOR SHIFT TRIP CNT
7
PHASE-TO-PHASE VOLTAGES
HI LO AV GR
V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQV
8
PHASE-TO-NEUTRAL VOLTAGES
HI LO AV GR
V(L1-N), V(L2-N), V(L3-N), V(L-N)EQV
9
MOVING AVERAGE VOLTAGE
HI LO
VM(L1-L2), VM(L2-L3), VM(L3-L1) OR VM(L1-N), VM(L2-N), VM(L3-N)
10
PHASE AND NEUTRAL CURRENTS
HI LO AV GR
I(L1), I(L2), I(L3), I(N)
11
ACTIVE POWER
HI LO AV GR
P(L1), P(L2), P(L3), P(TOT)
12
ACTIVE POWER IMBALANCE
HI LO AV GR
kW P1-P2, kW P2-P3, kW P3-P1
13
TREND GRAPH
P(TOT) LAST 24h
14
ACTIVE ENERGY – ACTIVE POWER – BAR GRAPH
kkWh (TOT) – kW (TOT) – BAR GRAPH kW(TOT)
15
REACTIVE POWER
HI LO AV GR
Q(L1), Q(L2), Q(L3), Q(TOT)
16
APPARENT POWER
HI LO AV GR
S(L1), S(L2), S(L3), S(TOT)
17
POWER FACTOR
HI LO AV GR
PF(L1), PF(L2), PF(L3), PF(TOT)
18
ENERGY METERS
PARTIAL
kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT)
19
ENERGY METERS PHASE L1
PARTIAL
kWh+L1(TOT), kWh-L1(TOT)
20
ENERGY METERS PHASE L2
PARTIAL
kWh+L2(TOT), kWh-L2(TOT)
21
ENERGY METERS PHASE L3
PARTIAL
kWh+L3(TOT), kWh-L3(TOT)
10
EVENT LOG
EVENT SCROLLING (128 EVENTS)
22
EXPANSION MODULES
23
INFO-REVISION-SERIAL NO.
MODEL, REV SW, REV HW, SER. No.
24
LOGO
–
Note:
some of the pages listed above may not be displayed, if the function displayed is not enabled. For example, if external CTs are not connected and programmed, the pages highlighted in grey are not
displayed.
–
Note:
the moving average voltage measurement is not available for the first 10 minutes after switching on or resetting the system. During this time, dashes and a countdown indicating the time left before
measurement display are shown.