P02.06
– If set to OFF, the display always remains on the page where the user left it. If set to a value, after this time the display returns to the page set with P02.07.
P02.07
– Abbreviation for the start page on switching on and that the display returns to automatically once the time P02.06 since a button was last pressed has elapsed.
P02.08
– Type of sub-page that the display returns to after P02.06 has elapsed.
M02 – UTILITY UoM Default Range
P02.01 Language English English
Italian
P02.02 LCD contrast % 60 0-100
P02.03 Display backlighting intensity high % 100 0-100
P02.04 Display backlighting intensity low % 30 0-50
P02.05 Low backlight delay s 30 5-600
P02.06 Default page return s 60 OFF / 10-600
P02.07 Default page SPI MEASURES Page list at page 4
P02.08 Default sub-page GR IN / HI / LO / AV / GR
P02.09 Display update time s 0.5 0.1 – 5.0
P03.01
– If set to OFF, password management is disabled.
P03.02
– With P03.01 active, value to specify to activate user-level access.
P03.03
– With P03.01 active, value to specify to activate advanced-level access.
M03 – PASSWORD UdM Default Range
P03.01 Enable passwords ON OFF-ON
P03.02 User-level password 1000 0-9999
P03.03 Advanced-level password 2000 0-9999
P04.01...P04.16, P04.20…P04.31
– Adjustment of trip thresholds and delay times defined by VDE-AR-N 4105 application guide.
Note: in case P04.23 is set to OFF (Vector shift disabled), a delay of 0.05s minimum is recommended for P04.25 (R.O.C.O.F delay) to avoid unexpected trip for R.O.C.O.F when a vector shift event occurs.
P04.17
– Maximum IS opening waiting time, before IS locking is recognised with consequent backup opening command.
P04.19
– IS restore (reset) time. IS reclosing delay time after all thresholds are ok again.
M04 – IP THRESHOLDS UoM Default Range
P04.01 UMAX U>> Threshold % 115 (P
≤
50kW) OFF – 100...130
125 (P>50kW)
P04.02 UMAX U> Threshold % 110 OFF – 100...120
P04.03 UMIN U< Threshold % 80 OFF – 20...100
P04.04 UMIN U<< Threshold % OFF (P
≤
50kW) OFF – 5...100
45 (P>50kW)
P04.05 UMAX U>> Delay s 0.10 0.05 - 1.00
P04.06 UMAX U> Delay s 0.10 0.05 - 100,00
P04.07 UMIN U< Delay s 0.10 (P
≤
50kW) 0.05 - 5.00
1.00 (P>50kW)
P04.08 UMIN U<< Delay s 0.30 0.05 - 5.00
P04.09 F MAX f>> Threshold Hz OFF OFF / 49.91 - 53.00
P04.10 F MAX f> Threshold Hz 51.50 OFF / 49.91 - 53.00
P04.11 MIN f< Threshold Hz 47.50 OFF / 45.01 - 50.00
P04.12 F MIN f<< Threshold Hz OFF OFF / 45.01 - 50.00
P04.13 F MAX f>> Delay s 0.10 0.05 - 5.00
P04.14 F MAX f> Delay s 0.10 0.05 - 100,00
P04.15 F MIN f< Delay s 0.10 0.05 - 100,00
P04.16 F MIN f<< Delay s 0.10 0.05 - 5.00
P04.17 Backup energizing delay s 0.5 0.1 – 10.0
P04.19 IP Restore delay s 60.00 0.04 – 300,00
P04.20 U> Type s AVG AVG
INST
P04.21 R.O.C.O.F threshold Hz/s 2.00 OFF / 0.01 – 5.00
P04.22 Validation cycles 25 5-50
P04.23 Vector Shift Threshold ° OFF OFF / 1 - 50
P04.24 R.O.C.O.F dead zone Hz 0.10Hz OFF / 0.01 – 0.50
P04.25 R.O.C.O.F delay s 0.00 0.00 - 2.00
P04.26 Vector shift delay s 0.00 0.00 - 2.00
P04.27 R.O.C.O.F / Vector shift delay on INP2 s 2.00 0.00 - 5.00
P04.28 UMAX reset threshold % 110 100 – 130
P04.29 UMIN reset threshold % 85 20 – 100
P04.30 FMAX reset threshold Hz 50.10 49.91 - 53.00
P04.31 FMIN reset threshold Hz 47.55 45.01 - 50.00
P01.12-13
– Second-level LSP (LSP2) threshold and delay.
P01.14
– Defines the automatic restore time after LSP tripping. If set to off, the system can only be restored manually by pressing the
s t
buttons.
P01.15
– Defines the function of the OUT4 output from those listed. The output is understood to be activated when conditions are normal (threshold not exceeded, alarm not active, etc.).
P01.16
– Defines the backup control mode, according to the logic in the Backup Activation Modes diagram on the final pages of this manual. If the backup is not used, set to OFF.
P01.17
– Backup opening pulse duration, when used in MODE C.
P01.18
– Normal status for remote tripping input.