IINTRODUCTION

The PMVF 80 equipment has been designed as an Interface Protection (IP) in accordance with VDE-AR-N 4105 and VDE V 0126-1-1 application guide. It can be applied to all LV generation systems (photovoltaic,

wind) where it is used to control the interface switch between generation system and public grid.

In the event of problems on the grid (e.g. due to maintenance), the system trips by opening the Interface switch (e.g. contactor) and isolating the generation system. In the event of Interface S  witch (IS) failure, it can

also control a backup device to disconnect the generation system in any case.

The equipment features 4 digital inputs permitting the connection of the system to the signals provided by the network operator to meet the requirements of the current regulations. The functions implemented and the

possibility of further expansion ensure that it is prepared for any developments to the protection system.

The PMVF 80 equipment is supplied already programmed and assembled. With the factory settings, once the connections have been made, it is ready for operation in compliance with the requirements of 

VDE-AR-N 4105 application guide without requiring any further settings to be made. It is nevertheless prepared for any future changes to the operating parameters. 

Changes to the settings are password protected, preventing tampering by unauthorised personnel. In case of damage or malfunctioning the device shall be returned to LOVATO Electric.

DESCRIPTION

–    Modular construction for DIN rail, 6 units.

–    LCD graphic 128x80 pixel, backlit, 4 grey levels.

–    Display and setting buttons.

–    Voltage measuring inputs three-phase + neutral.

–    Possibility of operation in the following line configurations:

•   Three-phase with neutral, VL-L voltage controls;

•   Three-phase with neutral, VL-N voltage controls;

•   Three-phase with neutral, VL-N + VL-L voltage controls (default);

•   Three-phase without neutral, VL-L voltage controls;

•   Single-phase, VL-N voltage control.

–    2 switching relay outputs to control:

•   OUT1: IS (Interface Switch) coil control;

•   OUT2: backup device control.

–    4 contact digital inputs for:

• INP1: IS feedback input;

• INP2: R.O.C.O.F and Vector Shift monitoring function inhibition;

• INP3: interface protection disabling signal;

• INP4: remote tripping control input.

–    Optional power unbalance limit (LSP) threshold control (current transformers required).

Two possible modes:

•  IS trip (OUT1) when LSP exceeded;

•  Separate output switching (OUT3) on additional expansion module for LSP trip indication.

–    Settings lock via 2-level changeable password.

–    Optional additional measurements, via connection of external CTs:

•  Currents;

•  Powers;

•  Energies supplied.

–    Setup for future installation of Interface module.

–    Programmable multifunctional output (OUT4) on additional expansion module.

TRIP THRESHOLDS

–    The voltage and frequency trip thresholds for which the equipment is set up according to the factory defaults are listed below. They correspond to the default requirements of  VDE-AR-N 4105 application guide.

PMVF 80 can be set to P

50kW or P>50kW cases by specific commands available in the command menu.

INDEX                                                                     

Pag.

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Trip thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Front button functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Displaying measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Table of display pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Password-protected access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Setting parameters (setup) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Parameter table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Commands Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

                                                                               

Pag.

Alarm indications and event list  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    9

Self-diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    9

Current, power and energy measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    9

Power Unbalance Limit (LSP) control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   10

Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   10

Wiring diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   10

Backup activation modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11

Terminal layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11

Mechanical dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11

Mounting and demounting instructions, symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11

Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   12

Voltage threshold

Default (%)

Default (s) 

Default (%)

Default (s)

P

50kW

P

50kW

P>50kW 

P>50kW

U max U>>

115

0.10s

125

0.10s

U max U>

110

0.10s

110

0.10s

U min U<

80

0.10s

80

1.0s

U min U<<

OFF

0.30s

45

0.30s

Frequency threshold

Default (Hz)

Default (Hz) 

Default (%)

Default (s)

P

50kW

P

50kW

P>50kW 

P>50kW

f max f>>

OFF

0.10s

OFF

0.10s

f max f>

51.5

0.10s

51.5

0.10s

f min f<

47.5

0.10s

47.5

0.10s

f min f<<

OFF

0.10s

OFF

0.10s

Loss of mains thresholds

Default

Validation time (cycles) 

Delay (s)

(islanding detection)

R.O.C.O.F (rate of change of frequency)

2Hz/s

0.50s (25)

0.00s

Vector shift

OFF

0.50s (25)

0.00s

Summary of Contents for PMVF 80

Page 1: ...den Vor jedem Eingriff am Instrument die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweckwidrigem Gebrauch der Vorrichtung bernimmt der Hersteller keine Haftun...

Page 2: ...ol OUT1 IS Interface Switch coil control OUT2 backup device control 4 contact digital inputs for INP1 IS feedback input INP2 R O C O F and Vector Shift monitoring function inhibition INP3 interface pr...

Page 3: ...ant information in both numerical and graphical form The limit thresholds are indicated by a small marker above the graphic bar while the arrows under the graphic bar indicate the measurement range HI...

Page 4: ...ACTIVE VOLTAGE THRESHOLDS AND DELAYS CURRENTLY ACTIVE R O C O F VECTOR SHIFT 4 IP TRIP COUNTER IS TRIP CNT BACKUP TRIP CNT REMOTE TRIP CNT POWER ON CNT IS OFF TIME 5 VOLTAGE THRESHOLD TRIP COUNTERS U...

Page 5: ...he settings In the normal measurements display press MENU to recall the main menu then select the password icon and press The password setting window shown below will appear Press the s t buttons to c...

Page 6: ...are used P01 05 Current of CT secondary winding P01 06 Type of connection and type of voltage control Program in line with the wiring P01 07 Rated active power of system If set to AUT the value is ca...

Page 7: ...Threshold 115 P 50kW OFF 100 130 125 P 50kW P04 02 UMAX U Threshold 110 OFF 100 120 P04 03 UMIN U Threshold 80 OFF 20 100 P04 04 UMIN U Threshold OFF P 50kW OFF 5 100 45 P 50kW P04 05 UMAX U Delay s 0...

Page 8: ...Alarm A03 enable ON ON OFF P06 04 Alarm A04 enable ON ON OFF P06 05 Alarm A05 enable ON ON OFF P06 06 Alarm A06 enable ON ON OFF COMMANDS MENU The Commands Menu is used to perform occasional operation...

Page 9: ...A04 INCORRECT MODULE HW CONFIGURATION PMVF 80 has not found the required expansion modules Check that they are configured correctly at the side A05 LSP1 TRIP PRESS s t TO RESTORE Power Imbalance Limi...

Page 10: ...connection of all the ISs auxiliary contacts In single phase wiring connect terminal V3 to VN Class 1 current transformers are recommended ATTENTION terminals A1 and A1 of EXM modules are connected in...

Page 11: ...s selected Backup output mirrors the IS output See parameter P01 16 M01 GENERAL MENU on page 6 TERMINAL LAYOUT MECHANICAL DIMENSIONS MM MOUNTING INSTRUCTION DEMOUNTING INSTRUCTION DEVICE SYMBOLS Warni...

Page 12: ...st be used with the same voltage source TECHNICAL CHARACTERISTICS Auxiliary supply Rated voltage Us 100 240V 110 250V Operating range 85 264V 93 5 300V Frequency 45 55Hz Power consumption dissipation...