Installation
Section 2
Canopy Ventilation Recommendations
C
B
18"-24"
457-610 mm
Capture Velocity
A
Capture
Velocity
D
E
F
Capture Area
Capture Area
(MIN)
(MIN)
(MIN)
Dimension
Single or Double Stack
Triple Stack *
A
96 in (2438 mm)
10 ft (3039 mm)
B (MIN)
8 in (203 mm)
22 in (559 mm)
C (MIN)
22 in (559 mm)
22 in (559 mm)
D
80 in (2032 mm)
6 ft 8 in (2032 mm)
E (MIN)
12 in (305 mm)
12 in (304 mm)
F
80 in (2032 mm)
6 ft 8 in AFF (2032 mm)
Exhaust Flow
1400 – 1600 CFM
—
AFF = Above Finished Floor
*
Hood dimensions shown are for island mount ‑ Size reductions may be possible for wall mount units.
NOTE: Hood dimensions and the positioning of the hood
over the oven will vary with hood manufacturers.
NOTE: Lincoln can provide oven spec sheets that show
the dimensions of the oven, kW or BTU ratings and other
information that will be useful to both the ventilation hood
supplier and the HVAC contractor.