Lifebreath 94-EXCHANGER Installation Instructions Manual Download Page 9

9

It is necessary to have balanced air flow in an HRV. The vol-
ume of air brought in from the outside must equal the volume
of air exhausted by the unit. If the air flow is not properly bal-
anced, then:

• The HRV may not operate at its maximum efficiency 
• A negative or positive air pressure may occur in the house
• The unit may not defrost properly
• Failure to balance HRV properly may void warranty

Excessive negative pressure

may have several undesirable

effects. In some geographic locations, soil gases such as
methane and radon gas may be drawn into the home through
basement/ground contact areas. 

Read the Application Warning in Clearances & Requirements sec-
tion of this manual!

Prior to balancing, ensure that:

1. All sealing of the duct system has been completed.

2. All of the HRV’s components are in place and 

functioning properly.

3. Balancing dampers are fully open.

4. Unit is on HIGH speed.

5. Air flow in branch lines to specific areas of the house

should be adjusted first prior to balancing the unit. A
smoke pencil used at the grilles is a good indicator of
each branch line's relative air flow.

6. After taking readings of both the stale air to the HRV duct

and fresh air to the house duct, the duct with the lower
CFM ([L/s] velocity) reading should be left alone, while the
duct with the higher reading should be dampered back to
match the lower reading.

7. Return unit to appropriate fan speed for normal operation

8. A field-supplied balancing damper for the stale air side

is required for system balancing.

Balancing Procedure

The following is a method of field balancing an HRV using a
Pitot tube, which is advantageous in situations when flow sta-
tions are not installed in the duct system. Procedure should
be performed with the HRV on high speed.

The first step is to operate the air handler on high speed. This
will provide the maximum pressure that the HRV will need to
overcome, and allow for a more accurate balance of the unit.

Drill a small hole in the duct (about 3/16"), three feet down-
stream of any elbows or bends, and one foot upstream of any
elbows or bends. These are recommended distances but the
actual installation may limit the amount of straight duct.

The Pitot tube should be connected to a magnehelic gauge or
digital manometer capable of reading from 0 to 0.25 in. (0-62
Pa) of water, preferably to 3 digits of resolution. The tube
coming out of the end of the Pitot is connected to the high
pressure side of the gauge. The tube coming out of the
branch of the Pitot is connected to the low pressure or refer-
ence side of the gauge.

Insert the Pitot tube into the duct; pointing the tip into the air
flow.

For general balancing it is sufficient to move the Pitot tube
around in the duct and take an average or typical reading.
Repeat this procedure in the other (supply or return) duct.
Determine which duct has the highest air flow (highest read-
ing on the gauge). Then damper that air flow back to match
the lower reading from the other duct. The flow should now
be balanced.

Actual air flow can be determined from the gauge reading.
The value read on the gauge is called the velocity pressure.
The Pitot tube comes with a chart that will give the air flow
velocity based on the velocity pressure indicated by the
gauge. This velocity will be in either feet per minute or meters
per second. To determine the actual air flow, the velocity is
multiplied by the cross sectional area of the duct being mea-
sured.

This is an example for determining the air flow in a 6" duct. 

The Pitot tube reading was 0.025 inches of water.

From the chart, this is 640 feet per minute.

The 6" duct has a cross sectional area of    

= [3.14 x (6"÷12)

2

]÷4

= 0.2 square feet

The air flow is then:

640 ft./min. x 0.2 square feet  = 128 cfm

For your convenience, the cross sectional area of some com-
mon round duct is listed below:

DUCT DIAM.

(inches)        

CROSS SECTION AREA

(sq. ft.)

5

0.14

6

0.20

7

0.27

The accuracy of the air flow reading will be affected by how
close to any elbows or bends the readings are taken.
Accuracy can be increased by taking an average of multiple
readings as outlined in the literature supplied with the Pitot
tube. 

Ensure balanced air flow in HRV. Excessive 
positive pressure may drive moist indoor air into 
the external walls of  the building where it may 
condense (in cold weather) and degrade 
structural components. May also cause key 
holes to freeze up. 

CAUTION

Ensure balanced air flow in HRV. Excessive 
negative pressure may also cause the back- 
drafting of vented combustion equipment.

WARNING

Air Flow Balancing 

Summary of Contents for 94-EXCHANGER

Page 1: ...air that is being exhausted to condition the fresh air as it is being brought in These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities who...

Page 2: ...635 mm is recommended for servicing unit DRAIN SPOUT 1 2 O D DRAINTUBING 1 2 I D TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT 1 2 O D 24 VOLT MOTORIZED DAMPER 1204 Engineering Data HRV Dimensions HRV inche...

Page 3: ...tor coupling with the damper shaft Align the damper in the fully closed position Using a 1 8 Allen key to tighten the set screw Dampers should now be in the fully closed position with no power Identif...

Page 4: ...eather Hood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weather Hood Requirements At least 6 2 m from the ventilation air intake At leas...

Page 5: ...recommended min 36 1m recommended min 6 2m recommended min 18 460mm min 18 460mm min OUTSIDE CORNER INTAKE EXHAUST INSIDE CORNER Weatherhood arrangement requires a minimum of 6 2m separation and a min...

Page 6: ...y be required to protect from condensate leakage The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point CAUTION Air Duct Design and...

Page 7: ...line to be switched To confirm the proper polarity use a voltmeter or test lamp to ensure there is no power after the switch when the door is open Check between that point and ground on the cabinet A...

Page 8: ...at highest operational speed 3 min recommended Insulated Duct DRAIN SPOUT TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern opens dampers to...

Page 9: ...unt of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube c...

Page 10: ...rnace running at highest operational speed MAGNEHELIC MAGNEHELIC Placement of Pitot Tube HRV MAGNEHELIC Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit with magnehelic gauge Pitot tube hose and...

Page 11: ...use dishwasher e install the clean filters f install clean core Note Core installation label on the outer end of the core To install the clean core a first mount the bottom flange of the core guide i...

Page 12: ...12 Date Maintenance Performed Contractor Notes Maintenance Record Note It is important to maintain this product regularly to ensure optimal performance...

Page 13: ...12 Date Entretien effectu Entrepreneur Notes Fiche d entretien Remarque pour un fonctionnement optimal il importe d entretenir ce produit r guli rement...

Page 14: ...s servez jamais du lave vaisselle e Remettez les filtres propres en place f R introduisez le noyau nettoy Remarque L tiquette d installation du noyau doit tre son extr mit ext rieure Pour installer le...

Page 15: ...ge des d bits d air avec tube de Pitot incluant un d bitm tre h lice un tuyau flexible et une mallette N B Ce sch ma n est offert qu des fins d illustration Les orifices de raccordement pour les canal...

Page 16: ...ongueur de conduit droit Le tube de Pitot devrait tre connect un d bitm tre h lice ou un autre manom tre capable de faire une lecture de 0 0 25 pouce d eau 0 62 Pa de pr f rence avec une pr cision all...

Page 17: ...t normalement quilibr alors que la fournaise fonctionne sa plus haute vitesse D SHUMIDISTAT DISTANCE qui exige deux fils s emploie partout o il y a beaucoup d humidit ouvre les registres pour assurer...

Page 18: ...qui doit tre commut e Pour confirmer que la polarit est appropri e servez vous d un voltm tre ou d une lampe de v rification pour vous assurer que lorsque la porte est ouverte le courant lectrique est...

Page 19: ...temp rature est maintenue au dessus du point de cong lation ATTENTION Conception et pose des conduites d air Quand l ensemble de canalisations est bien con u et cor rectement install on peut compter s...

Page 20: ...d un appareil de traitement de l air fournaise efficacit moyenne ou lev e au moins 6 pieds 2 m tres des voies d acc s des canalisations de remplissage du mazout des compteurs de gaz des bacs ordures...

Page 21: ...nseille d utiliser la pleine longueur des bandes entre le VRC et les solives de plancher Installation Toute erreur d installation de r glage de modification de r paration ou d entretien peut entra ner...

Page 22: ...igner automatiquement le raccord du moteur et l axe du registre Alignez le registre en position compl tement ferm e Utilisez une cl Allen de 1 8 po pour serrer la vis de fixa tion Les registres devrai...

Page 23: ...Le d bit d air habituel se situe entre 0 et 130 pieds cubes par minute Le d bit d air habituel se situe entre 80 et 130 pieds cubes par minute Date __________________________________________ tiquette...

Page 24: ...u on expulse pour conditionner l air neuf qui arrive Ces instructions ne constituent qu un guide g n ral et ne remplacent aucunement les exigences des codes en vigueur Consultez les autorit s locales...

Reviews: