Stale Air Exhaust System

The stale air exhaust system is accomplished by the posi-
tive pressure created in the furnace ducting. 

The air

handler blower must be running  for this system to be
effective. 

Drain Connection (HRV Only)

During a defrost cycle, the HRV may produce some con-
densation. This water should flow into a nearby drain, or
be taken away by a condensate pump. 

The HRV cabinet has  prepunched holes for the drain (see
below). Insert the drain spout through the hole in the drain
pan. Do not forget the “O ring” which seals each spout to
the pan. 

REMEMBER TO HAND TIGHTEN ONLY 

the

washer and lock nut which hold the drain spout in place.

Construct a P-Trap using the plastic tee connector. Cut
two lengths of hose and connect each piece to an end of
the “T” fitting, then connect the other ends to the two drain
spouts. Position the "T" fitting to point upward, andconnect
the drain line. Tape or fasten base to avoid any kinks. This
creates a “trap” which will hold some condensate and pre-
vent odours from being drawn up the hose and into the
fresh air supply of the HRV.

DRAIN

SPOUT

ZIP  TIE

TO DRAIN

TEE

CONNECTOR

DRAIN

SPOUT

PRE-PUNCHED HOLES (2)

DRAIN PAN

DRAIN PAN

1/2 " I.D. 

DRAIN HOSE

DRAIN HOSE PLUMBING

DRAIN

SPOUT

DRAIN

SPOUT

TO DRAIN

1/2" HARD PIPE

TEE

JOINT

PRE-PUNCHED HOLES (2)

DRAIN PAN

DRAIN PAN

HARD PIPE PLUMBING

"P" Trap (HRV only)

Note: Secondary drain pan may be required to 
protect from condensate leakage.

The HRV and all condensate lines must be 
installed in a space where the temperature is 
maintained above the freezing point. 

CAUTION

Air Duct Design and Installation

A well designed and installed ducting system will allow the
HRV to operate at its maximum efficiency.

Always try to keep duct runs as short and straight as pos-
sible. See Installation Diagrams for various installation
options.

The inner and outer liners of the flexible insulated duct
must be clamped to the sleeve of the weather hoods (as
close to the outside as possible) and the appropriate port
on the HRV. It is very important that the fresh air intake
line be given special attention to make sure it is well
sealed. A good bead of high quality caulking (preferably 

silicone sealant) will seal the inner flexible duct to both the
HRV port and the weather hood prior to clamping with a
large zip tie.

To minimize air flow restriction, the flexible insulated duct
that connects the two outside weather hoods to the HRV
should be stretched tightly and be as short as possible.

Twisting or folding the duct will severely restrict air flow.
See below for the recommended connection of flexible
insulated ducts to the the outside weather hoods and the
HRV.

Include a short length of fabric flex duct or other 
non-metallic connector in this hard ducted line 
in order to keep the HRV separately grounded 
(electrically) from the air handler. This will avoid 
a possible shock hazard to service people if a 
short to ground develops in one of the devices.

WARNING

Summary of Contents for 94-EXCHANGER

Page 1: ...air that is being exhausted to condition the fresh air as it is being brought in These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities who...

Page 2: ...635 mm is recommended for servicing unit DRAIN SPOUT 1 2 O D DRAINTUBING 1 2 I D TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT 1 2 O D 24 VOLT MOTORIZED DAMPER 1204 Engineering Data HRV Dimensions HRV inche...

Page 3: ...tor coupling with the damper shaft Align the damper in the fully closed position Using a 1 8 Allen key to tighten the set screw Dampers should now be in the fully closed position with no power Identif...

Page 4: ...eather Hood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weather Hood Requirements At least 6 2 m from the ventilation air intake At leas...

Page 5: ...recommended min 36 1m recommended min 6 2m recommended min 18 460mm min 18 460mm min OUTSIDE CORNER INTAKE EXHAUST INSIDE CORNER Weatherhood arrangement requires a minimum of 6 2m separation and a min...

Page 6: ...y be required to protect from condensate leakage The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point CAUTION Air Duct Design and...

Page 7: ...line to be switched To confirm the proper polarity use a voltmeter or test lamp to ensure there is no power after the switch when the door is open Check between that point and ground on the cabinet A...

Page 8: ...at highest operational speed 3 min recommended Insulated Duct DRAIN SPOUT TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern opens dampers to...

Page 9: ...unt of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube c...

Page 10: ...rnace running at highest operational speed MAGNEHELIC MAGNEHELIC Placement of Pitot Tube HRV MAGNEHELIC Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit with magnehelic gauge Pitot tube hose and...

Page 11: ...use dishwasher e install the clean filters f install clean core Note Core installation label on the outer end of the core To install the clean core a first mount the bottom flange of the core guide i...

Page 12: ...12 Date Maintenance Performed Contractor Notes Maintenance Record Note It is important to maintain this product regularly to ensure optimal performance...

Page 13: ...12 Date Entretien effectu Entrepreneur Notes Fiche d entretien Remarque pour un fonctionnement optimal il importe d entretenir ce produit r guli rement...

Page 14: ...s servez jamais du lave vaisselle e Remettez les filtres propres en place f R introduisez le noyau nettoy Remarque L tiquette d installation du noyau doit tre son extr mit ext rieure Pour installer le...

Page 15: ...ge des d bits d air avec tube de Pitot incluant un d bitm tre h lice un tuyau flexible et une mallette N B Ce sch ma n est offert qu des fins d illustration Les orifices de raccordement pour les canal...

Page 16: ...ongueur de conduit droit Le tube de Pitot devrait tre connect un d bitm tre h lice ou un autre manom tre capable de faire une lecture de 0 0 25 pouce d eau 0 62 Pa de pr f rence avec une pr cision all...

Page 17: ...t normalement quilibr alors que la fournaise fonctionne sa plus haute vitesse D SHUMIDISTAT DISTANCE qui exige deux fils s emploie partout o il y a beaucoup d humidit ouvre les registres pour assurer...

Page 18: ...qui doit tre commut e Pour confirmer que la polarit est appropri e servez vous d un voltm tre ou d une lampe de v rification pour vous assurer que lorsque la porte est ouverte le courant lectrique est...

Page 19: ...temp rature est maintenue au dessus du point de cong lation ATTENTION Conception et pose des conduites d air Quand l ensemble de canalisations est bien con u et cor rectement install on peut compter s...

Page 20: ...d un appareil de traitement de l air fournaise efficacit moyenne ou lev e au moins 6 pieds 2 m tres des voies d acc s des canalisations de remplissage du mazout des compteurs de gaz des bacs ordures...

Page 21: ...nseille d utiliser la pleine longueur des bandes entre le VRC et les solives de plancher Installation Toute erreur d installation de r glage de modification de r paration ou d entretien peut entra ner...

Page 22: ...igner automatiquement le raccord du moteur et l axe du registre Alignez le registre en position compl tement ferm e Utilisez une cl Allen de 1 8 po pour serrer la vis de fixa tion Les registres devrai...

Page 23: ...Le d bit d air habituel se situe entre 0 et 130 pieds cubes par minute Le d bit d air habituel se situe entre 80 et 130 pieds cubes par minute Date __________________________________________ tiquette...

Page 24: ...u on expulse pour conditionner l air neuf qui arrive Ces instructions ne constituent qu un guide g n ral et ne remplacent aucunement les exigences des codes en vigueur Consultez les autorit s locales...

Reviews: