Installation

NOTES:

1. Furnace blower is required to operate when ventilation is required. 
2.  Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required.
     Eighteen inches (460 mm) above grade minimum.
3.  Due to pressure differences in the equipment, airflows must be adjusted and confirmed on site.
4.  Maintenance should be performed twice a year or more if required.  Remove and wash filters and core and replace.  
   Outside hoods should be visually checked for blockage regularly.
5. Drain is required as shown above.
6. Built in balancing damper may require seasonal adjustments.

Forced 

Air 

Furnace

Outdoors

Cool Air

Return

Return Air

Built-in balancing damper* 
in both air streams.

*Unit is normally balanced with
furnace running at highest 
operational speed

3’ 

min.

recommended

Insulated 
Duct

DRAIN

SPOUT

TAPE

TO DRAIN

TEE

CONNECTOR

DRAIN

SPOUT

REMOTE DEHUMIDISTAT

*requires 2 wires

• anywhere humidity is a concern

• opens dampers to allow ventilation when humidity level exceeds 

selected setting

Part No. 99-130

Dehum

idistat 

Setting

 Relativ

e to 

Outside

 Conditio

ns

WINTER:

Set dehumidistat 

between 30% to 40%.

If home is too dry, 

adjust to higher setting. 

If home is too humid,

adjust to lower setting.

SUMMER:

Set dehumidistat 

to OFF.

Dehumidistat Operation

Low Voltage - 24 VAC

PROBLEMS

SOLUTIONS

Air is too dry

•  Increase humidity

•  Switch ventilation mode from continuous 

to intermittent

•  Install a humidifier

Air is too humid

•  Reduce the humidity

•  Verify if dryer is venting in basement

•  Verify if heating wood is stored in basement

•  Wait for outside temperature to change

Ex. Summer can be extremely humid

•  Verify balancing of the HRV

•  Run furnace blower continuously to increase 

ventilation rate

Summary of Contents for 94-EXCHANGER

Page 1: ...air that is being exhausted to condition the fresh air as it is being brought in These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities who...

Page 2: ...635 mm is recommended for servicing unit DRAIN SPOUT 1 2 O D DRAINTUBING 1 2 I D TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT 1 2 O D 24 VOLT MOTORIZED DAMPER 1204 Engineering Data HRV Dimensions HRV inche...

Page 3: ...tor coupling with the damper shaft Align the damper in the fully closed position Using a 1 8 Allen key to tighten the set screw Dampers should now be in the fully closed position with no power Identif...

Page 4: ...eather Hood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weather Hood Requirements At least 6 2 m from the ventilation air intake At leas...

Page 5: ...recommended min 36 1m recommended min 6 2m recommended min 18 460mm min 18 460mm min OUTSIDE CORNER INTAKE EXHAUST INSIDE CORNER Weatherhood arrangement requires a minimum of 6 2m separation and a min...

Page 6: ...y be required to protect from condensate leakage The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point CAUTION Air Duct Design and...

Page 7: ...line to be switched To confirm the proper polarity use a voltmeter or test lamp to ensure there is no power after the switch when the door is open Check between that point and ground on the cabinet A...

Page 8: ...at highest operational speed 3 min recommended Insulated Duct DRAIN SPOUT TAPE TO DRAIN TEE CONNECTOR DRAIN SPOUT REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern opens dampers to...

Page 9: ...unt of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube c...

Page 10: ...rnace running at highest operational speed MAGNEHELIC MAGNEHELIC Placement of Pitot Tube HRV MAGNEHELIC Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit with magnehelic gauge Pitot tube hose and...

Page 11: ...use dishwasher e install the clean filters f install clean core Note Core installation label on the outer end of the core To install the clean core a first mount the bottom flange of the core guide i...

Page 12: ...12 Date Maintenance Performed Contractor Notes Maintenance Record Note It is important to maintain this product regularly to ensure optimal performance...

Page 13: ...12 Date Entretien effectu Entrepreneur Notes Fiche d entretien Remarque pour un fonctionnement optimal il importe d entretenir ce produit r guli rement...

Page 14: ...s servez jamais du lave vaisselle e Remettez les filtres propres en place f R introduisez le noyau nettoy Remarque L tiquette d installation du noyau doit tre son extr mit ext rieure Pour installer le...

Page 15: ...ge des d bits d air avec tube de Pitot incluant un d bitm tre h lice un tuyau flexible et une mallette N B Ce sch ma n est offert qu des fins d illustration Les orifices de raccordement pour les canal...

Page 16: ...ongueur de conduit droit Le tube de Pitot devrait tre connect un d bitm tre h lice ou un autre manom tre capable de faire une lecture de 0 0 25 pouce d eau 0 62 Pa de pr f rence avec une pr cision all...

Page 17: ...t normalement quilibr alors que la fournaise fonctionne sa plus haute vitesse D SHUMIDISTAT DISTANCE qui exige deux fils s emploie partout o il y a beaucoup d humidit ouvre les registres pour assurer...

Page 18: ...qui doit tre commut e Pour confirmer que la polarit est appropri e servez vous d un voltm tre ou d une lampe de v rification pour vous assurer que lorsque la porte est ouverte le courant lectrique est...

Page 19: ...temp rature est maintenue au dessus du point de cong lation ATTENTION Conception et pose des conduites d air Quand l ensemble de canalisations est bien con u et cor rectement install on peut compter s...

Page 20: ...d un appareil de traitement de l air fournaise efficacit moyenne ou lev e au moins 6 pieds 2 m tres des voies d acc s des canalisations de remplissage du mazout des compteurs de gaz des bacs ordures...

Page 21: ...nseille d utiliser la pleine longueur des bandes entre le VRC et les solives de plancher Installation Toute erreur d installation de r glage de modification de r paration ou d entretien peut entra ner...

Page 22: ...igner automatiquement le raccord du moteur et l axe du registre Alignez le registre en position compl tement ferm e Utilisez une cl Allen de 1 8 po pour serrer la vis de fixa tion Les registres devrai...

Page 23: ...Le d bit d air habituel se situe entre 0 et 130 pieds cubes par minute Le d bit d air habituel se situe entre 80 et 130 pieds cubes par minute Date __________________________________________ tiquette...

Page 24: ...u on expulse pour conditionner l air neuf qui arrive Ces instructions ne constituent qu un guide g n ral et ne remplacent aucunement les exigences des codes en vigueur Consultez les autorit s locales...

Reviews: