41
Indoor unit priority control method
The air conditioner forcefully operated by demand power control function operates in wind only
mode during cooling operation, and stops during heating operation.
But, even if the air conditioner operation is changed by forced operation, it operates in a way that
the user does not feel the change in terms of the effect of the cooling or heating.
While the air conditioner is forcefully operated by demand power control function, it uses the au-
tomatic control of the central control method, air conditioner cannot be operated individually.
But, if the current operation state uses the power under the target operation ratio setting value,
air conditioner can be individually controlled.
To control demand power, click ‘Demand’ menu at the top of LG ACCS.
When you click ‘Demand’ menu, the following demand power control screen appears.
CAUTION
When there is no demand menu
• When there is no ‘demand power’ menu in ACCS menu, and instead, there is a ‘Peak Con-
trol’ menu, the ACP setting is set to use peak control function. To use demand power
function, change the setting of the ACP by referring to ‘selecting peak or demand’.
!