Part 4 Trouble Shooting
- 91 -
Copyright © 2019 - 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Purpose
Generation of an error caused by DC
link voltage detection error.
Items for checking
1. Checking DC link voltage detection error
1. Set the tester in DC Voltage Mode and check the voltage.
2. Checking the voltage between DC Link detection signal and Micom GND.
3. The standard of normal voltage measurement is 2.4~2.8 V.
4. If the measurement is different from the standard, replace PCBA.
! Caution
: When the measurement is made in the state that the electricity is applied, check the tester
for being in the measurement mode and be careful to avoid possible short of the parts other
than the measuring part.
Apply the electricity.
Turn indoor devices off.
Measure voltage.
Replace PCBA.
Current detection
part is normal.
Checking method
Within 2.4 ~ 2.8 V
❈
PCBA : PCB Assembly
Yes
No
DC Link Detection Circuit
6.7 Troubleshooting Outdoor Error
CH 21 (DC Peak / Comp IPM Fault)