6.7 Troubleshooting Outdoor Error
CH 24 High pressure switch error
CH24(High pressure switch error) / System is turned off by outdoor unit high pressure switch error
n
How to check High pressure switch error
1. Defective high pressure switch
2. Defective fan of indoor unit or outdoor unit
3. Check valve of compressor clogged
4. Pipe distortion due to the pipe damage
5. Refrigerant overcharge
6. Defective EEV at the indoor or outdoor unit
7. Covering or clogging
(Outdoor covering during the cooling mode / Indoor unit filter clogging during the heating mode)
8. SVC valve clogging
9. Defective outdoor PCB
Purpose
Excessive rise of discharge pressure in outdoor compressor
Items for checking
Compressor off due to the high pressure switch in outdoor unit