Part 2 Functions & Controls
- The above table shows the correlation between the air flow rate and E.SP.
- Be sure to set the value by referring to the table above. Incorrect setting values can cause malfunction.
- The values in the table are based on electrical rated conditions. Therefore, if there is a fluctuation in voltage,
the air flow rate may change.
Chassis
Capacity
[kBtu/h]
Grade Step CMM
Static Pressure [mmAq(Pa)]
4(39) 5(49) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06
32:07
32:08
32:09
32:10
32:11
M2
36
Standard
Compact
LOW
24
88
91
95
100 101 108
113
115
118
118
118
MID
28
93
97
101 105 108
115
118
120
124
124
124
HIGH
32
101 105 109 112 115
119
123
126
128
128
128
M3
48
Standard
Compact
LOW
28
74
76
79
82
89
92
94
96
99
102
107
MID
34
78
82
84
89
94
96
98
101
104
106
112
HIGH
40
83
89
92
94
98
100
102
105
108
110
116
M3
48
High
LOW
28
74
76
79
82
89
92
94
96
99
102
107
MID
34
78
82
84
89
94
96
98
101
104
106
112
HIGH
40
83
89
92
94
98
100
102
105
108
110
116
M3
36
High
LOW
28
74
76
79
82
89
92
94
96
99
102
107
MID
34
78
82
84
89
94
96
98
101
104
106
112
HIGH
40
83
89
92
94
98
100
102
105
108
110
116
M3
42
High
LOW
28
74
76
79
82
89
92
94
96
99
102
107
MID
34
78
82
84
89
94
96
98
101
104
106
112
HIGH
40
83
89
92
94
98
100
102
105
108
110
116
M3
60
Standard
Compact
LOW
40
82
89
92
94
98
100
102
105
108
110
113
MID
45
90
92
96
98
102 104
106
109
112
114
117
HIGH
50
94
97
100 104 107 109
112
115
117
119
121
Chassis
Capacity
[kBtu/h]
Grade Step CMM
Static Pressure [mmAq(Pa)]
5(49) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 14(137) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06
32:07
32:08
32:09
32:10
32:11
M2
42
Standard
Compact
LOW
28
100 103 106 110 114
118
121
125
128
133
136
MID
33
108 111 114 118 122 125
128
131
134
138
140
HIGH
38
117 120 124 127 130 133
135
138
140
144
147