Part 2 Functions & Controls
1.1 Hot start
• When heating is started, the indoor fan is stopped or very slow to prevent the cold air carry out
• When the temp. of heat exchanger reach 30 °C(model by model), indoor fan is started.
4.2 Self-diagnosis Function
• The air conditioner installed can self-diagnosed its error status and then transmits the result to the central control.
Therefore, a rapid countermeasure against failure of the air conditioner allows easy management and increases the
usage life of air conditioner.
• Refer to trouble shooting guide.
4.3 Soft dry operation
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and
the setting temp is automatically set according to the intake air temperature.
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10 minutes dehumidification
operation and 4 minutes compressor off repeat.
Compressor ON Temp.
‘
Setting Temp+0.5 °C
Compressor OFF Temp.
‘
Setting Temp-0.5 °C
• In 10-minute dehumidification operation, the indoor fan operates with the low airflow speed.
4. Reliability
Intake air Temp. Setting Temp.
26 °C ≤ intake air temp. 25 °C
24 °C ≤ intake air temp.< 26 °C intake air temp. -1 °C
22 °C ≤ intake air temp. < 24 °C intake air temp. -0.5 °C
18 °C ≤ intake air temp. < 22 °C intake air temp.
intake air temp. < 18 °C 18 °C