Part 4 Trouble Shooting
- 109 -
Copyright © 2019 - 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
6.7 Troubleshooting Outdoor Error
n
Flow of trouble diagnosis
Is high pressure switch
connector connected
to PCB?
No
Note 1)
Note 2)
Note 2)
Connect securely
Is high pressure switch
connector short
during off time?
Yes
No
Is this error appeared
again after reset?
Yes
No
Is SVC valve open?
Yes
Re-check momentary
problem or not
Replace connecting cable
Open SVC valve
No
Yes
Is high pressure switch
terminal short?***
No
Replace high pressure switch
Yes
Is high pressure
more than 4 000 kPaG
at manifold gauge?
No
Replace PCB
Yes
Is high pressure of
LGMV similar as
at manifold gauge?
No
Replace high pressure switch
Yes
Check pipe is blocked or
not and take measure