8
7.
PARAMETER CODE (HEX)
<Common>
: Area accessible regardless of inverter models (Note 2)
Parameter
Address
Parameter Name
Unit
Read/Write
Data Value (Hex)
0000
Inverter model
-
R
4: SV-iS5 3:SV-IH
SV-iS5
0: 0.75 1:1.5 2:2.2 3: 3.7 4: 5.5
5: 7.5 6: 11 7: 15 8: 18.5 9: 22
A: 30 B:37 C:45 D: 55 E: 75 F: 90
10: 110 11: 132 12: 160 13: 200 14: 220
15: 280 16:375 (Unit: kW)
0001 Inverter
capacity
- R
SV-IH
A: 30 B: 37 C: 45 D: 55 E: 75 F: 90
10: 110 11: 132 12: 160 14: 220
(Unit: kW)
0002
Inverter Input Voltage
-
R
0: 220V 1: 440V
0003 S/W
Version - R
SV-iS5
0100: Ver. 1.00, 0101: Ver 1.01
SV-iH
0200 : Ver. 2.00, 0201: Ver. 2.01
0004 Parameter
Lock - R/W
0: Lock (default)
1: Unlock
0005 Frequency
Reference
0.01Hz
R/W
0-60000
0006 Run
Command
- R/W
Bit 0: Stop
Bit 1: Forward Run
Bit 2: Reverse Run
Bit 3: Fault Reset
Bit 4: Emergency Stop
(Bit 0 also resets fault)
0007 Acceleration
Time
0.1
sec
R/W
0008 Deceleration
Time
0.1
sec
R/W
0009
Output Current
0.1 A
R
000A
Output Frequency
0.01 Hz
R
000B
Output Voltage
0.1 V
R
000C
DC Link Voltage
0.1 V
R
000D
Output Power
0.1 kW
R
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]