COMMUNICATION PROTOCOL
Use LG RS485 protocol (Open protocol). Contact LG representatives.
Computer or other hosts can be Master and inverters Slave. Inverter responds to Read/Write
command from Master.
5.1.
Supported command codes
Function Code
Name
‘R’ Parameter
Read
‘W’ Parameter
Write
‘X’ Monitor
Register
‘Y’ Monitor
Execution
(Important: Use ASCII CODE (Capital Letter).)
5.2.
BroadCast Function
Use it to send command to all inverters at the network.
All inverters respond when command is sent from Station # 255.
5.3.
Error Code
Error Code
Display
Description
ILLEGAL
FUNCTION
IF Invalid
command
received.
ILLEGAL DATA
ADDRESS
IA
Invalid parameter address received.
Monitor executed without resistoring monitor.
ILLEGAL DATA
VALUE
ID
Invalid data received.
WRITE MODE
ERROR
WM
Read Only or not-programmable during run.
FRAME ERROR
FE
Frame size, internal Num or Sum is different.
TIME OUT
ERROR
TO
DPRAM communication failed for the set time.
DPRAM OFF LINE
DO
DPRAM is Off-line.
INVALID ID
NUMBER
IN Different
address
received.
UNDEFINED
CONDITION
UC Undefined
condition
received.