10
Parameter
Address
Parameter Name
Unit
Read/Write
Data Value (Hex)
0010
Input Terminal Status
-
R
SV-iS5
Bit 0: P1, Bit 1: P2, Bit 2: P3
Bit 3: P4, Bit 4: P5, Bit 5: P6,
Bit 6: RST, Bit 7: BX, Bit 8: JOG, Bit 9:
FX, Bit 10: RX
SV-iH
Bit 0: FX Bit 1:RX Bit 2:BX
Bit 3: RST Bit 8: P1 Bit 9: P2
Bit 10: P3 Bit 11: P4
Bit 12: P5 Bit 13: P6
0011
Output Terminal Status
-
R
Bit 0: Q1 (OC1) , Bit 1: Q2 (OC2)
Bit 2: Q3 (OC3)
SV-iS5
Bit 3: AUX Bit 4: 30AC
SV-iH
Bit 3: AUX1 Bit 4: AUX2
x0012 V1 -
R
SV-iS5 0 – FFC0
SV-iH 0-FFFF
0x0013 V2 -
R
SV-iS5 0 – FFC0
SV-iH 0-FFFF
0x0014 I -
R
SV-iS5 0 – FFC0
SV-iH 0- FFFF
0x0015 RPM -
R
(Note 2)
The changed value in Common affects the current setting but returns to the previous setting when power is
cycled or Inverter is reset. However, changing value is immediately reflected in other parameter groups even in the case
of Reset or Power On/Off.