Installation Manual
9
Installation
ENGLISH
Installation
Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good.
• There should not be any heat source or steam near the
unit
Confirm the positional relationship between the unit and
suspension bolts.
• Installation the ceiling opening to clean the filter or servi
ce
under the product.
Selection of the best location
A(Min)
Inspection hole
(600 x 600)
Control box
H=20 or more
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Side view
(unit: mm)
600
600
B
B(Min)
(Unit: mm)
Top view
Air outlet
Air outlet
(Unit: mm)
Capacity (kBtu/h)
A
B
5/7/9
600
800
12/15/18
600
1000
21/24
600
1200
- The appliance shall be installed, operated and stored in a room
with a floor area larger than the minimum area.
- Use the graph of table to determine the minimum area.
Minimum floor area
0
100
200
300
400
500
600
Amin (m
2
)
m (kg)
0
1.22
4
2
3
4
5
6
7
8
Floor standing
Wall mounted
Ceiling mounted
(for R32)
Ceiling
Service Space
A
B
Summary of Contents for MULTI V ARNU05GL4G4
Page 21: ...R32 R410A ...
Page 43: ......
Page 65: ...R32 R410A ...
Page 87: ......
Page 109: ...R32 R410A ...
Page 131: ......
Page 153: ...R32 R410A ...
Page 175: ......
Page 197: ......
Page 219: ......
Page 241: ......
Page 263: ......
Page 285: ......
Page 307: ......
Page 329: ......
Page 331: ......