10
Indoor Unit
Installation
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to absorb
unnecessary vibration.
• Apply a filter Accessory at air return hole.
※
Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
• A place where the unit will be leveled and that can support
the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
POSITION OF SUSPENSION BOLT
(Unit:mm)
Dimension
Capacity(kBtu/h)
A
B
C
D
E
F
G H
I
J
L4
733 772 338 460 36 190 20 660 148 700
L5
933 972 338 460 36 190 20 860 148 900
L6
1133 1172 338 460 36 190 20 1060 148 1100
C
E
G
D
F
I
A
J
B
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4
X 8
H
Drainage hole
POSITION OF CONSOLE BOLT
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant additional refrigerant amount
- Amin : minimum area for installation
Floor location
m (kg) Amin (m
2
)
< 1.224
-
1.224
12.9
1.4
16.82
1.6
21.97
1.8
27.80
2
34.32
2.2
41.53
2.4
49.42
2.6
58.00
2.8
67.27
3
77.22
3.2
87.86
3.4
99.19
3.6
111.20
3.8
123.90
4
137.29
4.2
151.36
4.4
166.12
Floor location
m (kg) Amin (m
2
)
4.6
181.56
4.8
197.70
5
214.51
5.2
232.02
5.4
250.21
5.6
269.09
5.8
288.65
6
308.90
6.2
329.84
6.4
351.46
6.6
373.77
6.8
396.76
7
420.45
7.2
444.81
7.4
469.87
7.6
495.61
7.8
522.04
Wall mounted
m (kg) Amin (m
2
)
< 1.224
-
1.224
1.43
1.4
1.87
1.6
2.44
1.8
3.09
2
3.81
2.2
4.61
2.4
5.49
2.6
6.44
2.8
7.47
3
8.58
3.2
9.76
3.4
11.02
3.6
12.36
3.8
13.77
4
15.25
4.2
16.82
4.4
18.46
Wall mounted
m (kg) Amin (m
2
)
4.6
20.17
4.8
21.97
5
23.83
5.2
25.78
5.4
27.80
5.6
29.90
5.8
32.07
6
34.32
6.2
36.65
6.4
39.05
6.6
41.53
6.8
44.08
7
46.72
7.2
49.42
7.4
52.21
7.6
55.07
7.8
58.00
Ceiling Mounted
m (kg) Amin (m
2
)
< 1.224
-
1.224
0.956
1.4
1.25
1.6
1.63
1.8
2.07
2
2.55
2.2
3.09
2.4
3.68
2.6
4.31
2.8
5.00
3
5.74
3.2
6.54
3.4
7.38
3.6
8.27
3.8
9.22
4
10.21
4.2
11.26
4.4
12.36
Ceiling Mounted
m (kg) Amin (m
2
)
4.6
13.50
4.8
14.70
5
15.96
5.2
17.26
5.4
18.61
5.6
20.01
5.8
21.47
6
22.98
6.2
24.53
6.4
26.14
6.6
27.80
6.8
29.51
7
31.27
7.2
33.09
7.4
34.95
7.6
36.86
7.8
38.83
Summary of Contents for MULTI V ARNU05GL4G4
Page 21: ...R32 R410A ...
Page 43: ......
Page 65: ...R32 R410A ...
Page 87: ......
Page 109: ...R32 R410A ...
Page 131: ......
Page 153: ...R32 R410A ...
Page 175: ......
Page 197: ......
Page 219: ......
Page 241: ......
Page 263: ......
Page 285: ......
Page 307: ......
Page 329: ......
Page 331: ......