- 95 -
(3) Gas Charging
(After Evacuation)
• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect-
ed from the vacuum pump to the valve at the
bottom of the cylinder.
- If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
2. Purge the air from the charge hose.
- Open the valve at the bottom of the cylinder and
press the check valve on the charge set to
purge the air. (Be careful of the liquid refriger-
ant). The procedure is the same if using a gas
cylinder.
3. Open the low handle on the gauge and charge
the system with liquid refrigerant.
- If the system can not be charged with the speci-
fied amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from
the gas side valve's service port.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
5. Mount the valve stem nuts and the service port
nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
Charging
cylinder
Check valve
manifold gauge
Hi- handle
(CLOSE)
Low-
handle
(OPEN)
Indoor unit
Outdoor unit
Liquid side
Gas side
Open
3-way
valve
Closed
3-way
valve
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
Summary of Contents for HPCI-C35E
Page 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Page 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Page 112: ... 112 3 Convertible Type Indoor Unit ...
Page 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Page 114: ... 114 18k ...
Page 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Page 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Page 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Page 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Page 139: ...P No 3828A20097S February 2004 Printed in Korea ...