- 30 -
5. Auto Operation
• The operation procedure is as following. (Cooling & Heating Model)
If initial mode is decided, that mode is continued without the room temperature changing.
For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.
• Auto Operation for Cooling. (Cooling only Model)
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speed
are automatically decided by Fuzzy rule.
Setting temperature
Intake-air
temperature
Operation Mode
Heating
Soft Dry
Cooling
Operation Condition
Intake-air Temperature
Setting temperature
Fan speed
Air Direction Control
Over 26°C
25°C
Over 24°C~below 26°C
Intake air -1°C
Over 22°C~below 24°C
Intake air -0.5°C
Over 20°C~below 22°C intake air temperture
below 20°C
20°C
Over 20°C~below 30°C
Fuzzy control
below 20°C
20°C
over 30°C
30°C
below 21°C
below
24°C
~
Over 24°C
Over
21°C
When Auto Operation
initial start
When pressing room temp-
erature setting button
during Auto Operation
Controlled
by Fuzzy logic
In this mode, when
pressing the verti-
cal air diretion con-
trol.
Button, louvers
moves to 1/f
rhythm (refer to
page 17)
Intake-Air temp
Setting Temp. +0.5°C
(Compressor OFF)
Setting Temp.-0.5°C
(Compressor ON)
Indoor Fan
Compressor
ON
ON
OFF
OFF
Fuzzy Speed
Summary of Contents for HPCI-C35E
Page 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Page 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Page 112: ... 112 3 Convertible Type Indoor Unit ...
Page 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Page 114: ... 114 18k ...
Page 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Page 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Page 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Page 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Page 139: ...P No 3828A20097S February 2004 Printed in Korea ...