The problem of missing the connector (SUB PCB ASSY)
Connectors
CN-UVW
CN-IPM
Condition
OPEN
OPEN
• Stop compressor.
CN-Gate 1, 2
OPEN
• Malfunctions inverter circuit
• The operation LED blink 9 times.
• Malfunctions inverter circuit.
• Stop compressor and outdoor fan.
• The operation LED blinks 8 times.
Problem (error mode)
■
The problem of missing the connector (OUTDOOR MAIN PCB ASSY)
Connectors
CN-POWER
CN-AC
CN-DC
CN-IPM
CN-GND
CN-FAN
CN-TH
CN-COMP
Condition
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN/SHORT
OPEN/SHORT
• Malfunctions outdoor unit.
• Stop compressor and outdoor fan.
• Malfunctions outdoor unit.
• Stop compressor and outdoor fan.
• The operation LED blinks 10 times.
• Malfunctions inverter circuit.
• Stop compressor and outdoor fan.
• The operation LED blinks 8 times.
• Malfunctions EMI /EMS
CN-Gate 1, 2
OPEN
• Malfunctions inverter circuit
• The operation LED blinks 9 times.
• Malfunctions fan.
• The operation LED blinks twice.
• The LED01K blinks 10 times.
• Continue Comp. operation.
(when the discharge pipe TH opens)
• Stop Comp. operation
(when the discharge pipe TH shorts)
• Malfunctions outdoor unit.
• Stop compressor and outdoor fan.
• The operation LED blinks 10 times.
Problem (error mode)
Summary of Contents for HPCI-C35E
Page 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Page 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Page 112: ... 112 3 Convertible Type Indoor Unit ...
Page 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Page 114: ... 114 18k ...
Page 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Page 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Page 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Page 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Page 139: ...P No 3828A20097S February 2004 Printed in Korea ...