- 93 -
(1) Pumping down
•
Procedure
1. Confirm that both the gas side and liquid side
valves are set to the open position.
- Remove the valve stem caps and confirm that
the valve stems are in the raised position.
- Be sure to use a hexagonal wrench to operate
the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then con-
nect the manifold gauge to the service port of
the gas side valve.
- Connect the hose of the gauge with the push
pin to the service port.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge
slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.
6. Operate the air conditioner at the cooling cycle
and stop it when the gauge indicates 1kg/cm
2
g.
7. Immediately set the gas side valve to the closed
position.
- Do this quickly so that the gauge ends up indi-
cating 1kg/
g.
8. Disconnect the charge set, and mount the liquid
side and gas side valve caps and the service
port nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)
- Be sure to check for gas leakage.
manifold gauge
Hi- handle
(CLOSE)
Low-handle
(CLOSE)
Indoor unit
Outdoor unit
Liquid side
Gas side
Open
3-way
valve
Closed
3-way
valve
Summary of Contents for HPCI-C35E
Page 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Page 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Page 112: ... 112 3 Convertible Type Indoor Unit ...
Page 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Page 114: ... 114 18k ...
Page 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Page 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Page 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Page 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Page 139: ...P No 3828A20097S February 2004 Printed in Korea ...